69
Troubleshooting
OMMG00012
Rev 12 – NOV 2019
Section 8
Troubleshooting
Contents
Para
Page
Checklist .................................................................................. 69
Positioner Status Indicator ............................................... 71
Positioner Error Signal ..................................................... 71
Positioner Replacement .............................................................. 72
8.1
Checklist
The following table lists a number of possible faults that could be observed in
the system, with the relevant diagnostic and remedial actions.
Fault Indication
Diagnostic Action
Remedial Action
Valve is oscillating or
moving in large steps
Check PID values on PID
Controller
Adjust PID values
Check dead band settings on
PID Controller
Adjust dead band settings
Check location of
temperature sensor is away
from bends and junctions
Move temperature sensor
Check deadband setting of
the actuator (section 4.6,
page 34)
Adjust deadband setting
Switch off power, remove
actuator lid, and check that
gears are tight (Fig 13, page
Adjust gears
Check coupling pin (Fig 10,
page 30, item 6)
Replace pin
Valve drives in one
direction only
Check electrical connections
Check operation of relays
Replace relay
Check power to actuator
Check control system and
temperature sensor
Check setting of
Potentiometer (4.8.7, page
Adjust position feedback
sensor
Summary of Contents for 10GEF
Page 2: ......
Page 14: ...14 System Overview Rev 12 NOV 2019 OMMG00012...
Page 52: ...52 Electric Actuator Rev 12 NOV 2019 OMMG00012...
Page 54: ...54 PID Controller Rev 12 NOV 2019 OMMG00012...
Page 64: ...64 System Integration Rev 12 NOV 2019 OMMG00012 Fig 22 System Wiring Diagram 8072D Controller...
Page 67: ...67 System Integration OMMG00012 Rev 12 NOV 2019...
Page 68: ...68 System Integration Rev 12 NOV 2019 OMMG00012...
Page 74: ...74 Technical Data Rev 12 NOV 2019 OMMG00012 9 1 1 Valve Bore Fig 25 Valve Selection Curve...