37
Electric Actuator
OMMG00012
Rev 12 – NOV 2019
Fig 12
Actuator mounting
Removal
WARNINGS
Lethal voltages are present in the actuator presenting a shock hazard
to personnel. Ensure the power supply to the actuator is isolated
before the cover is removed.
If an actuator is removed from a valve fitted in a live system, the valve
rotor may rotate uncontrollably in the body. An actuator must never
be removed from a valve installed in a live system.
The actuator case can be hotter than the ambient temperature. Care
must be taken when handling the actuator to prevent burn injuries to
personnel.
1
Switch off and isolate the actuator electrical supplies.
2
Manually operate the actuator to the low temperature position.
3
Remove the actuator cover.
4
Label the wires to aid reassembly, disconnect from the terminal strip and
pull the cables clear from cable entries.