AMF² 36K + HMI 08.2013
Page 53 of 71
√
44
Filter 1 Index Backward Alarm #44
The Index piston is not unlocked after a forward
command. The controller performs a second trial to
push the piston and during this trial this alarm
message is displayed.
√
45
Filter 1 Index Forward Att. #45
The Index piston is not locked after a backward
command. The controller performs a second trial to
push the piston and during this trial this alarm
message is displayed.
√
46
Filter 1 Piston Movement SW2 to SW1 #46
The main piston started to move from SW2 to SW1
but the movement is not completed. This fault
message is issued only after an unsuccessful second
trial to push the piston by the controller. This is a
fault status of the specific filter, since the other
filter is still operational the system issues only an
alarm message.
The following table lists and describes the possible system fault messages that may appear on the controller’s status
screens.
ID #
Message Text
Remarks
0
No Fault
1
System Fault #1
All the AMF² filters in the system are disabled or in
fault mode.
2
No Pump Available #2
The back-flush pumps are in fault mode or in OFF
position
4
Low Inlet Pressure #4
The Inlet Pressure is lower than the minimum
required for starting a flushing cycle.
5
HDP Fault #5
The differential pressure across the AMF² filters
exceeds the HDP preset value
Summary of Contents for AMF-36K
Page 16: ...Figure 25 ...
Page 17: ...AMF 36K HMI 08 2013 Page 17 of 71 ...
Page 23: ...AMF 36K HMI 08 2013 Page 23 of 71 1 3 ...
Page 65: ...AMF 36K HMI 08 2013 Page 65 of 71 5 3 Control cabinet drawings ...
Page 66: ...AMF 36K HMI 08 2013 Page 66 of 71 ...
Page 67: ...AMF 36K HMI 08 2013 Page 67 of 71 ...
Page 68: ...AMF 36K HMI 08 2013 Page 68 of 71 ...
Page 69: ...AMF 36K HMI 08 2013 Page 69 of 71 ...