AMF² 36K + HMI 08.2013
Page 50 of 71
Configuration Screen – Page 2
This screen allows the operator to set:
Continue Filtering During Fault
– This parameter sets the filter
behavior during fault mode. The user can select to continue the
filtering during fault or to stop the filtration by closing the inlet
and outlet valves of the filter. Please note that if the filter is
faulty and the filtering continues the filter could become totally
blocked.
Close Inlet Valve While not Filtering
– This parameter sets the
filter behavior while not filtering (such as in Pause or Idle modes).
The user can select to keep the inlet valve in such cases opened
or closed.
Setup Screen – Page 1
This screen allows the operator to set:
Filter Type
– The user may select between AMF² 36 or Lab. Test.
For normal operation of the filter tis filed
must be AMF² 36
.
Number of Piston Steps
– The user may set the number of piston
strokes per flushing cycle. For normal operation of the filter this
parameter
must be 36.
Solenoid Type
– The user may select the type of solenoids
installed at the filter’s solenoids cabinet.
Never set this
parameter to the wrong type
.
System’s Filter Configuration
– If the filter is an independent
single filter this parameter should be set to
Single
. However if the
filter is part of a multi filters installation this parameter should be
set to
Multi.
Note:
This HMI Version supports a single installation only
Flush. Pump Protect.
– The user can set the type of the flushing
pump protection device. It can be set to Float or Pressure. The
default protection device is a pressure meter installed at the
pump’s outlet. However if the pump feeding line is connected to
a tank with a tank level float, this parameter should be set to
Float.
Note:
Setting this field to the wrong parameter may cause the
filter to cease operation.
Summary of Contents for AMF-36K
Page 16: ...Figure 25 ...
Page 17: ...AMF 36K HMI 08 2013 Page 17 of 71 ...
Page 23: ...AMF 36K HMI 08 2013 Page 23 of 71 1 3 ...
Page 65: ...AMF 36K HMI 08 2013 Page 65 of 71 5 3 Control cabinet drawings ...
Page 66: ...AMF 36K HMI 08 2013 Page 66 of 71 ...
Page 67: ...AMF 36K HMI 08 2013 Page 67 of 71 ...
Page 68: ...AMF 36K HMI 08 2013 Page 68 of 71 ...
Page 69: ...AMF 36K HMI 08 2013 Page 69 of 71 ...