AMF² 36K + HMI 08.2013
Page 48 of 71
Valves 2 Screen
This screen allows the operator to set the:
Inlet Valve Opening Delay –
Set the delay for opening the inlet
valve of the filter. (Default value - 10 seconds.)
Filtering to Waste Duration
– Set the required time for the
“filtering to waste” stage (V7). (Default value - 55 seconds.)
Filtering to Waste Closing Delay
– Set the required time for
closing the “filtering to waste” Valve (V7). (Default value - 10
seconds.)
Outlet Valve Opening Delay –
Set the delay for opening the
outlet valve of the filter. (Default value - 10 seconds.)
Delay between Filters -
Set the delay in 10 seconds units
between the ends of the flush cycle of one unit to the start of the
cycle of the next unit. (Default value 1 X 10 seconds.) Not
applicable in a single filter installation.
Operations Screen
This screen allows the operator to:
Step by Step
– Start a “Step by Step” back-flush process of the
AMF² filter.
This is a necessary part of the first startup operation of the filter
during its installation process.
AMF Cycles for M303 Flushing
– N/A in a single AMF² 36 filter
M303 Flush Counter
- N/A in a single AMF² 36 filter
Filter Operation
– Enable / Disable the filter operation. Usually
used in multi-filters installation.
Restore Factory Defaults
- Use this option to reset the system’s
parameters to their factory defaults.
Summary of Contents for AMF-36K
Page 16: ...Figure 25 ...
Page 17: ...AMF 36K HMI 08 2013 Page 17 of 71 ...
Page 23: ...AMF 36K HMI 08 2013 Page 23 of 71 1 3 ...
Page 65: ...AMF 36K HMI 08 2013 Page 65 of 71 5 3 Control cabinet drawings ...
Page 66: ...AMF 36K HMI 08 2013 Page 66 of 71 ...
Page 67: ...AMF 36K HMI 08 2013 Page 67 of 71 ...
Page 68: ...AMF 36K HMI 08 2013 Page 68 of 71 ...
Page 69: ...AMF 36K HMI 08 2013 Page 69 of 71 ...