Setup Screen – Page 2
This screen allows the operator to set:
Filter-to-waste After Pause / Idle
– This parameter is used to set
the number of filters on which a “Filtering to waste” operation
should be performed whenever the system exits a Pause or Idle
mode. This parameter is used regularly in multi-filter installations
and in cases where an extra care is needed in order to ensure the
supply of clean water. This action ensures that the filtered water
volume that stayed in the filter during the pause/idle period will
not reach the consumer.
Minimum Inlet Press. For Flushing
– This parameter allows the
user to set a minimum inlet pressure for sufficient flushing
process. This parameter is useful in cases where the filter is
flushed with an unstable water source. Entering a value at this
field would ensure that the filter is flushed only if there is a
sufficient pressure. Enter 9999 for disabling this option.