Local Operation
3-10
TM-F2OP-C1XN-01
Notes:
1. If switch SW1-7 is ON but there is no signal applied, the S/D LED
turns on and the power supply will not provide an output until the
HIGH signal level is applied.
2. Any of the eight switches on SW1 is OFF (OPEN) when it has been
flipped up to break contact, ON (CLOSED) when flipped down to
close contact.
Table 3-2
Switch Settings for Shutdown Circuit Logic
Switch SW1-7 Setting
Source
Signal
Signal
Level
Supply
Output
S/D LED
OFF (OPEN)
(Active low, default)
2-15 V
HIGH
OFF
ON
0-0.4 V
LOW
ON
OFF
ON (CLOSED)
(Active high)
2-15 V
HIGH
ON
OFF
0-0.4 V
LOW
OFF
ON