2

FOREWORD

The design of model BBCN375T754NV complies with the current edition 

of ANSI Z21.10.3/CSA 4.3 as automatic storage or automatic circulating 

tank type water heaters.

Installation diagrams are found in this manual.  These diagrams will serve 

to provide the installer with a reference for the materials and method of 

piping necessary.  It is highly essential that all water and gas piping be 

installed as shown on the diagrams.

In addition to these instructions, the equipment shall be installed in 

accordance with those installation regulations in force in the local area 

where the installation is to be made.  These shall be carefully followed 

in all cases.  Authorities having jurisdiction should be consulted before 

installations are made.

ROUGH-IN DIMENSIONS

FIGURE 1.

The installation must conform to these instructions and the local code 

authority having jurisdiction.  

In the absence of local codes, the installation must comply with the following:

In the United States:

Current edition of the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 

and the National Electrical Code, NFPA 70;

In Canada:

Current edition of the Installation Code CAN/CSA-B149.1 and the 

Canadian Electrical Code CSA C22.1.

These are available from Canadian Standards Association, 8501 East 

Pleasant Valley Road, Cleveland, OH 44131 or National Fire Protection 

Association, 1 Batterymarch Park, Quincy, MA 02269.

*INSTALL IN ACCORDANCE WITH LOCAL CODES

TOP VIEW

TABLE 3, GAS AND ELECTRICAL CHARACTERISTICS

All Models:  Maximum supply pressure = 14.0 in. W.C. (3.48 kPa)

 

Minimum supply pressure, Natural gas = 6 in. W.C. (1.49 kPa). 

 

Minimum pressures must be maintained under both load and no load (static and dynamic) conditions.

Recovery ratings are based on 80% thermal efficiency. 

TABLE 1, DIMENSIONS

Units

A

B

C

D

E

F

G

H

J

K

L

M

Inches

CM

66 5/8

169.22

58 3/4

134.23

30 15/16

78.58

27 3/4

70.5

15 1/4

38.6

4

10.2

15 3/4

40.0

16

40.6

1 1/4

3.2

1 1/4

NPT

1/2

NPT

12 1/4

31.1

TABLE 2, RECOVERY RATINGS

Manifold Pressure

Electrical Characteristics

Type of gas

Inches W.C.

kPa

Voltz/Hz

Amperes

Natural Gas

4.0

1.12

120/160

<5

INPUT RATE

Recovery in US Gallons/hr or Liters/hr at Indicated Temperature Rise in Fahrenheit or Celsius

75,100    BTU/H

°F

30

40

50

60

70

80

90

100

110

120

130

140

GPH

243

182

145

122

104

91

81

73

66

60

56

52

22           KW

°C

17

23

28

33

39

44

50

56

61

67

72

78

LPH

920

688

549

460

392

344

306

277

251

228

213

199

Summary of Contents for BBCN375T754NV 100 Series

Page 1: ...AL ULTRA LOW NOx GAS WATER HEATER Glass Lined Tank type Water Heater INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE T...

Page 2: ...Canada Current edition of the Installation Code CAN CSA B149 1 and the Canadian Electrical Code CSA C22 1 These are available from Canadian Standards Association 8501 East Pleasant Valley Road Clevel...

Page 3: ...r and Igniter 12 Checking Gas Input 12 Vent System 12 Blower Maintenance 13 Relief Valve 13 Hot Water Odor 13 Winter Protection 13 Replacement Parts 13 PREVENTIVE MAINTENANCE 13 14 Procedure for Perio...

Page 4: ...gas in excess of the safe limits This could result in serious injury or death Contact your local gas supplier for any specific changes that may be required in your area Upon completion of derating of...

Page 5: ...THROUGH THE CHIMNEY OR VENT PIPE The venting of the water heater should be inspected by a qualified service technician at the time of installation and periodically thereafter to ensure a down draft c...

Page 6: ...t of the vent system are exposed to ambient temperatures below 35 degrees F 2 degrees C it must be insulated to prevent condensation Do not connect the heater to a common vent or chimney with solid fu...

Page 7: ...E LOCATION TO AVOID SCALDING OR WATER DAMAGE THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS DO NOT...

Page 8: ...having jurisdiction AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION If any of the original wire as supplied with the appliance must be replaced use only t...

Page 9: ...matic gas valve while heater is operating TABLE 5 Type of Gas Input Manifold Pressure Natural 75 100 Btu hr 22 KW hr 4 0 in W C 1 12 kPa OPERATION It is recommended that a qualified person perform the...

Page 10: ...as been under water OPERATING INSTRUCTIONS A Set thermostat to the lowest setting B Turn off all the electric power to the appliance if service is to be performed TO TURN OFF GAS TO APPLIANCE BEFORE O...

Page 11: ...akage corrosion and other deficiencies which could cause an unsafe condition 3 So far as is practical close all building doors and windows and all doors between the space in which the water heater s c...

Page 12: ...rn doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous conditions of use 7 If improper venting is observed during any of the above tests the venting syst...

Page 13: ...anode as necessary to maintain corrosion protection For further information contact your dealer WINTER PROTECTION In regions where freezing weather is encountered all water must be drained from unit...

Page 14: ...the Flo Jug kit This screw is to be installed in the vent hole when Flo Jug is not in use Remove drain valve from heater and insert a 3 4 x 4 nipple Connect and clamp 1 I D x 3 hose to Flo Jug and hea...

Page 15: ...idence of poor vent action Possible causes are too long a vent pipe or improper chimney operation 3 If the leakage is from the temperature and pressure relief valve or its discharge pipe it may repres...

Page 16: ...information and tables may serve to answer your question about a problem that you are having without having to call a service agent For your safety water heater service should be performed only by a q...

Page 17: ...a qualified person for service 3 Thermostat problems A Thermostat set too low Set temperature control higher B Thermostat or ECO defective Replace gas control valve thermostat C High limit control ci...

Page 18: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Page 19: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Page 20: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Page 21: ...21 NOTES...

Page 22: ...22 NOTES...

Page 23: ...hod of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES U...

Page 24: ...nson City TN 37605 Phone 800 456 9805 Fax 800 999 5210 www americanwaterheater com Copyright 2012 American Water Heater Company All rights reserved www americanwaterheater com American Water Heater Jo...

Reviews: