TROUBLESHOOTING
Table 8-1 UTx-M Troubleshooting Table
Symptom
Possible Cause
How to Verify
Corrective Action
UTx-M gas
reading does
not show up
on 1DBX
Monitor
Incorrect
Modbus
Address
specified in
either the
Monitor or the
UTx
Monitor shows UTx-M gas
sensor missing.
Enter password, enter TX
menu and correct MODBUS
address for sensor.
Duplicate
Modbus
Address on two
or more UTx-M
devices on
MODBUS
network.
Monitor shows UTx-M gas
sensor missing.
UTx-M with same MODBUS
addresses show slow blinking
Green network LEDs, while
other UTx-M units on network
detect Network Fault by
blinking their Network LED
Red.
Enter password, enter TX
menu and correct MODBUS
address for sensor.
Incorrect Device
or gas type
specified in the
Digital Monitor
Monitor shows gas mis-match
by turning off its Green
System LED. Check monitor’s
system status in “Get System
Info.” dialog.
Change monitor’s
configuration to match
Sensor Module gas and
MODBUS address settings.
UTx-M S1 is CO and S2 is
NO2. Ensure MODBUS
addresses are matching for
assignment S1 and S2.
Incorrect Parity
UTx-M shows Red on
Network LED
Monitor’s MODBUS interface
are set to EVEN parity.
Check appropriate MODBUS
interface configuration in “Set
Interface”, “RS485 Port”…
Change UTx-M parity to
match Monitor’s EVEN
Parity.
Incorrect Baud
Rate selected
UTx-M shows Red on
Network LED
Monitor’s MODBUS interface
are set to 9600 Baud. Check
appropriate MODBUS
interface configuration in “Set
Interface”, “RS485 Port”…