![AMC AMC-SM-91A01 User Manual Download Page 11](http://html1.mh-extra.com/html/amc/amc-sm-91a01/amc-sm-91a01_user-manual_2921111011.webp)
AMC-UTx-M-xx-400 Series Digital Transmitter
11
2.1.2.2 Carbon Monoxide/ Nitrogen Dioxide
Gas Type………………………………….….…..
CARBON MONOXIDE (CO) / NITROGEN
DIOXIDE (NO2)
Smart Sensor 2 Module Order Number
….……
AMC-SM-VCA01
Operating Temperature ………………………
-20° to 40° C
Sensor Height Above Finished Floor (as part
of Digital Transmitter)
4-6 Feet (1.22-1.52m)
Sensor
Life…….…………………………………
Up to 2 Years
(CO element up to 6 years)
Sensor Warranty………………………………..
2 Years
Range …………………………...……………
0-100ppm CO
0-10ppm NO2
Zero Buffering of Display……………………..
<5ppm C2
<0.5ppm NO2
Calibration Kit
Part Number…………………..
AMC-C1-FM1
Default Calibration Gas……………………….
100ppm CO
10ppm NO2
Gas Flow Rate…………………………………..
0.5L/min.