background image

7

System Evacuation

Safe Refrigerant Handling

1. Connect the vacuum pump, high vacuum manifold

set with high vacuum hoses, thermocouple vacuum
gauge and charging cylinder as shown. Begin with
all valves fully closed.

2. If service dill valves are used for evacuation, use a

core remover to lift the valve core.  It provides
greater efficiency.

3. Confirm proper pump and gauge operation. Open

the shutoff valve which leads to the high vacuum
gauge manifold. Start the pump. When the com-
pound gauge (low side) reading drops approximately
29 inches of vacuum, open the valve to the thermo-
couple vacuum gauge and evacuate until the gauge
reads 250 microns or less.

4. Close the valve to the thermocouple vacuum gauge.

This avoids potential gauge damage from “pegging
the meter”.

5. Open the high and low side valves on the gauge

manifold. Keeping the valve on the charging cylinder
closed, open the valve on the gauge manifold that
leads to the cylinder.

6. Evacuate the system to about 29 inches Hg as mea-

sured by the compound (low side) gauge.

7. Open the valve to the thermocouple vacuum gauge.

Evacuate until the gauge reads 250 microns or less.

8. Close the valve to the vacuum pump. Wait five min-

utes, then check the pressure on the thermocouple
vacuum gauge:

a. If the pressure is not more than 1500 microns, the

system is leak-free and properly evacuated. Pro-

ceed to Step 9.

b. If the pressure rises, but holds at about 5000 mi-

crons, moisture and noncondensibles are still

present. Open the valve to the vacuum pump, and

go back to Step 7.

c. If the pressure rises above 5000 microns, a leak is

present. Refer to the previous section “Leak Test-

ing”.

9. Close the valve to the thermocouple vacuum gauge.

Close the valve to the vacuum pump. Shut off the
pump.

A.  LOW SIDE VALVE

B.  HIGH SIDE VALVE
C.  VACUUM PUMP
D.  THERMOCOUPLE GAUGE
E.  MANIFOLD GAUGE
F.  CHARGING CYLINDER

C

A

B

E

D

HIGH VACUUM PUMP

LARGE DIAMETER

BRAIDED VACUUM

HOSES

TO

RELATED

GAUGE

PORTS OF 

COND. UNIT

HIGH VACUUM

MANIFOLD

LOW SIDE

GAUGE

HIGH SIDE

GAUGE

DIAL-A-CHARGE

CHARGING CYLINDER

THERMOCOUPLE
VACUUM
GAUGE

F

Figure 3

Summary of Contents for REMOTE HEAT PUMP

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Page 3: ...nce and service If possible discuss unit location with the owner before proceeding This unit is for outdoor installation only It cannot be completely enclosed Refer to Figure 1 for clearances from the...

Page 4: ...Avoid burying refrigerant lines If you must bury them first dig the trench so it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separatel...

Page 5: ...Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all refrigerants must BY LAW be reclaimed If an indoor leak is suspected thoroughly ventilate the area before...

Page 6: ...a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge mani fold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach...

Page 7: ...ylinder 6 Evacuate the system to about 29 inches Hg as mea sured by the compound low side gauge 7 Open the valve to the thermocouple vacuum gauge Evacuate until the gauge reads 250 microns or less 8 C...

Page 8: ...e drop to a maxi mum of 2 from the main breaker or fuse panel to the outdoor unit A thermostat is required 1 To connect the unit to the power supply route the power supply and ground wires through the...

Page 9: ...compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding additional refrigerant to a system add only...

Page 10: ...chart shows a superheat of 20 F is ideal for these conditions Since our superheat is 30 20 10 F higher than ideal charge must be added If the system is performing properly reinstall the service port c...

Page 11: ...fter servicing is completed disconnect the power move the Defrost Time Select Tab back to 30 60 or 90 remove jumper wire on DFS and reconnect the power NOTES 1 If the time select tab remains in TEST p...

Page 12: ...ITE GREEN TYPICAL H P ROOM THERMOSTAT SYSTEM COMPOSITE DIAGRAM 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R INDOOR UNIT R RED 2 1 OT 1 OT 2 3 EHR 1 2...

Page 13: ...14 Does the compressor sound normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do c...

Page 14: ...14 2003 2004 Goodman Company L P August 2004...

Reviews: