background image

13

System Checklist

1 Does the condenser fan blade rotate freely, and is it tight on the shaft?

2

Does the refrigerant tubing flex freely and not touch another tube to cause rub 
through?

3 Are both indoor and outdoor sections level?

4 Are the units properly supported?

5 Is outdoor section properly located on concrete base or equivalent?

6

Are the refrigerant lines correctly installed according to the relative position of the 
outdoor and indoor sections?

7 Is the refrigerant tubing properly supported by isolation hangers?

8 Is the system completely free of refrigerant leaks?

9 Has the system been properly evacuated?

10 Does the system have the correct refrigerant charge?

11

Is the outdoor unit protected by the correct size time delay type fuses or 
breakers in the indoor power box?

12 Are the power supply wires to units the correct size?

13 Are all electrical connections tight?

14 Does the compressor sound normal?

15

Check the amperage on the indoor blower motor.  Is it within the limits shown on 
the nameplate of the motor?

16 Are all access panels installed and secured?

17

Do controls function properly? Are manual reset switches in the reset position 
(high pressure cutouts, relays, etc.)?

18

Check the voltage with unit running.  Does it check within the tolerance of 207 to 
253V for 230V, or 198 to 228V?  If using 208V power indoors, have you modified 
the transformer wiring as necessary? 

19 Has the air flow across  the indoor coil been checked and adjusted?

20

Has the air distribution system been balanced?  Are all grilles, diffusers, and 
dampers properly adjusted and locked?

21 Has the system operated at least 30 minutes before leaving the job?

22 Does the owner understand the operation of the unit and the thermostat?

23 Does the owner know where the filters are located?

24 Does the owner know when and how the filter(s) should be cleaned or changed?

26 Does the owner know whom to call for service?

27 Has the User's Guide been filled out and left with the owner?

Summary of Contents for REMOTE HEAT PUMP

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Page 3: ...nce and service If possible discuss unit location with the owner before proceeding This unit is for outdoor installation only It cannot be completely enclosed Refer to Figure 1 for clearances from the...

Page 4: ...Avoid burying refrigerant lines If you must bury them first dig the trench so it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separatel...

Page 5: ...Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all refrigerants must BY LAW be reclaimed If an indoor leak is suspected thoroughly ventilate the area before...

Page 6: ...a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge mani fold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach...

Page 7: ...ylinder 6 Evacuate the system to about 29 inches Hg as mea sured by the compound low side gauge 7 Open the valve to the thermocouple vacuum gauge Evacuate until the gauge reads 250 microns or less 8 C...

Page 8: ...e drop to a maxi mum of 2 from the main breaker or fuse panel to the outdoor unit A thermostat is required 1 To connect the unit to the power supply route the power supply and ground wires through the...

Page 9: ...compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding additional refrigerant to a system add only...

Page 10: ...chart shows a superheat of 20 F is ideal for these conditions Since our superheat is 30 20 10 F higher than ideal charge must be added If the system is performing properly reinstall the service port c...

Page 11: ...fter servicing is completed disconnect the power move the Defrost Time Select Tab back to 30 60 or 90 remove jumper wire on DFS and reconnect the power NOTES 1 If the time select tab remains in TEST p...

Page 12: ...ITE GREEN TYPICAL H P ROOM THERMOSTAT SYSTEM COMPOSITE DIAGRAM 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R INDOOR UNIT R RED 2 1 OT 1 OT 2 3 EHR 1 2...

Page 13: ...14 Does the compressor sound normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do c...

Page 14: ...14 2003 2004 Goodman Company L P August 2004...

Reviews: