background image

9

IMPORTANT!

See the wiring diagram or the Product Data Book applicable
to your model* to determine if this unit has a crankcase
heater. If it does, you must connect electrical power to the
unit for four hours before operating the compressor.
Failure to do so could result in compressor damage.
During all installation and service work, follow all
regulations of the Environmental Protection Agency. (This
system uses R-22 - an HCFC [Hydrogenated
Chlorofluorocarbon].) Violation of EPA regulations may
result in fines or other penalties.

Preliminary Charge Adjustment

Use a male hex head wrench (3/16” for liquid, 5/16” for
suction) to carefully open the suction and liquid valve stem
on the unit. These valves do not back seat. OPEN EACH
VALVE ONLY UNTIL THE TOP OF THE STEM IS 1/8”
FROM THE RETAINER. TO AVOID LOSS OF REFRIG-
ERANT, DO NOT APPLY PRESSURE TO THE RETAINER.
The outdoor unit is factory-charged with enough R-22 for
the matching indoor blower coil or matching A-coil 

plus 

15

feet of 3/8” liquid line. For liquid line lengths greater than 15
feet, add 0.55 oz. of R-22 per additional foot up to 50 feet.
For line sets over 50 feet consult an Amana

®

 distributor.

For liquid line lengths less than 25 feet, subtract 0.55 oz.
of R-22 per deviating foot.

IMPORTANT: 

Use only refrigerant which is certified to

meet ARI Standard 700. Used refrigerant may cause
compressor damage, and will void the warranty. (Most
portable machines cannot clean used refrigerant well
enough to meet this ARI Standard.)

IMPORTANT

: If adding additional refrigerant to a system,

add only refrigerant vapor (not liquid) through the suction
valve (low side) on the outdoor unit. Any other practice may
cause compressor damage.

System Startup

Final Charge Adjustment

(Matching Systems-Cooling Operation)

IMPORTANT: Never operate the compressor with the
suction valve closed to “test the compressor’s pumping
efficiency”. In some cases, this can result in serious
compressor damage and loss of warranty coverage.

If installing a non-matching system, the outdoor tempera-
ture must be 60°F or higher to perform the final charge
adjustment.
If the outdoor temperature is 60°F or higher, set the room
thermostat to COOL, fan switch to AUTO, and set the
temperature control well below room temperature.
Turn the electrical power on, and let the system run for
several minutes. It will take some time for the refrigerant
pressures to stabilize.
If you are using the “Matched Combination”, see the
Product Data Book applicable to your model*. Compare
the operating pressures and outdoor unit amp draw to the
numbers listed. If pressures and amp draw are too low, add
charge. If pressures and amp draw are too high, remove
charge.
If you are not using the “Matched Combination” which is
listed on the Product Data Book applicable to your model*,
check subcooling (TEV coils) or superheat (cap tube or
flowrator coils) as detailed in the following section.

Summary of Contents for REMOTE HEAT PUMP

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Page 3: ...nce and service If possible discuss unit location with the owner before proceeding This unit is for outdoor installation only It cannot be completely enclosed Refer to Figure 1 for clearances from the...

Page 4: ...Avoid burying refrigerant lines If you must bury them first dig the trench so it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separatel...

Page 5: ...Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all refrigerants must BY LAW be reclaimed If an indoor leak is suspected thoroughly ventilate the area before...

Page 6: ...a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge mani fold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach...

Page 7: ...ylinder 6 Evacuate the system to about 29 inches Hg as mea sured by the compound low side gauge 7 Open the valve to the thermocouple vacuum gauge Evacuate until the gauge reads 250 microns or less 8 C...

Page 8: ...e drop to a maxi mum of 2 from the main breaker or fuse panel to the outdoor unit A thermostat is required 1 To connect the unit to the power supply route the power supply and ground wires through the...

Page 9: ...compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding additional refrigerant to a system add only...

Page 10: ...chart shows a superheat of 20 F is ideal for these conditions Since our superheat is 30 20 10 F higher than ideal charge must be added If the system is performing properly reinstall the service port c...

Page 11: ...fter servicing is completed disconnect the power move the Defrost Time Select Tab back to 30 60 or 90 remove jumper wire on DFS and reconnect the power NOTES 1 If the time select tab remains in TEST p...

Page 12: ...ITE GREEN TYPICAL H P ROOM THERMOSTAT SYSTEM COMPOSITE DIAGRAM 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R INDOOR UNIT R RED 2 1 OT 1 OT 2 3 EHR 1 2...

Page 13: ...14 Does the compressor sound normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do c...

Page 14: ...14 2003 2004 Goodman Company L P August 2004...

Reviews: