background image

10

System Startup

Final Charge Adjustment

(Non-Matching Systems—Cooling Operation)

I

NDOOR

 C

OIL

 

WITH

 E

XPANSION

 V

ALVE

:

At stabilized cooling conditions and with an outdoor tem-
perature of 60°F or higher, the subcooling at the outdoor
unit liquid line service valve should be subcooling 9 - 15°.
Add or remove charge as required.

I

NDOOR

 C

OIL

 

WITH

 O

RIFICE

 

OR

 C

AP

 T

UBE

For a proper superheat reading, measure the refrigerant
pressure and temperature at the outdoor unit vapor line
service valve.  The superheat should be within 3°F of that
shown on the 

Desired Superheat vs Outdoor Temperature

Chart

.  If the superheat is higher, add charge. If the

superheat is lower, remove charge.

EXAMPLE

: The low side pressure is 84 psi. The low side

temperature is 80°F. The outdoor temperature is 95°F.
The indoor temperature is 85°F. By referring to a pressure
temperature chart, you will see that 84 psi equals a
saturated temperature of 50°F. The superheat is 80 - 50 =
30°F. The chart shows a superheat of 20°F is ideal for
these conditions. Since our superheat is 30 - 20 = 10°F
higher than ideal, charge must be added.

If the system is performing properly, reinstall the service
port caps and the valve bonnets.  With the valve opened,
the valve bonnet is the primary seal against refrigerant
leaks. Apply two drops of clean oil to the cap threads,
allowing the oil to run down to the inner cap seal surface.
Close caps finger-tight.  Then tighten cap an additional two
to three hex flats.  

NOTE: 

 Subsequent opening and

replacement of the cap will require only 1/2 to 1 hex flat.
See the table below for the torque required for an effective
seal on the valve bonnet (1/6 turn past finger tight).

Tubing Size

Torque (Foot-Pounds)

3/8

10

1/2, 5/8, 3/4

14

 7/8, 1 1/8

16

After closing the valve bonnet, perform a final refrigerant
leak test on the valves and sweat connections.  Return the
room thermostat to the desired settings.

4

50

60

70

80

90

100

110

120

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

SUP

E

RHE

AT

 @

 O

.D.

 UN

IT

OUTDOOR TEMPERATURE

DESIRED SUPERHEAT vs OUTDOOR TEMPERATURE

90° F

 Ind

oor

70

° F

 In

do

or

75

° F

 In

do

or

80°

 F In

do

or

85°

 F In

do

or

Summary of Contents for REMOTE HEAT PUMP

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Page 3: ...nce and service If possible discuss unit location with the owner before proceeding This unit is for outdoor installation only It cannot be completely enclosed Refer to Figure 1 for clearances from the...

Page 4: ...Avoid burying refrigerant lines If you must bury them first dig the trench so it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separatel...

Page 5: ...Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all refrigerants must BY LAW be reclaimed If an indoor leak is suspected thoroughly ventilate the area before...

Page 6: ...a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge mani fold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach...

Page 7: ...ylinder 6 Evacuate the system to about 29 inches Hg as mea sured by the compound low side gauge 7 Open the valve to the thermocouple vacuum gauge Evacuate until the gauge reads 250 microns or less 8 C...

Page 8: ...e drop to a maxi mum of 2 from the main breaker or fuse panel to the outdoor unit A thermostat is required 1 To connect the unit to the power supply route the power supply and ground wires through the...

Page 9: ...compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding additional refrigerant to a system add only...

Page 10: ...chart shows a superheat of 20 F is ideal for these conditions Since our superheat is 30 20 10 F higher than ideal charge must be added If the system is performing properly reinstall the service port c...

Page 11: ...fter servicing is completed disconnect the power move the Defrost Time Select Tab back to 30 60 or 90 remove jumper wire on DFS and reconnect the power NOTES 1 If the time select tab remains in TEST p...

Page 12: ...ITE GREEN TYPICAL H P ROOM THERMOSTAT SYSTEM COMPOSITE DIAGRAM 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R INDOOR UNIT R RED 2 1 OT 1 OT 2 3 EHR 1 2...

Page 13: ...14 Does the compressor sound normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do c...

Page 14: ...14 2003 2004 Goodman Company L P August 2004...

Reviews: