background image

6

Leak Testing

WARNING

To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gasses for leak testing of a
refrigeration system.

Safe Refrigerant Handling

WARNING

To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure
relief valve.  The pressure relief valve must be set to open at  no more than 150 psig.

1. Be sure both hand valves on the gauge manifold are

closed relative to the center port (i.e., turned in all
the way.)  Attach this gauge manifold to the service
valves on the unit (see Figure 2). Do not open the
unit service valves.  Do not use refrigerant from the
unit for leak testing - it has been precisely measured
at the factory for optimum performance.

2. Connect a cylinder of dry nitrogen to the center port

on the gauge manifold.

3. Open the hand valve a minimal amount on the line

coming from the nitrogen cylinder.

4. Open the high pressure valve on the gauge mani-

fold. Pressurize the refrigerant lines and the indoor
coil to 150 psig (1034 kPA).  To reach 150 psig, you
may need to further open the hand valve on the ni-
trogen cylinder.

WARNING

To avoid possible explosion or equipment damage,
do not exceed 150 psig when pressure testing.

After you reach 150 psig, close the valve on the nitrogen
cylinder. Disconnect it from the gauge manifold.  If you plan
to use an electronic leak detector, add a trace of R-22 to the
system (if permitted by current EPA regulations).

5. Place a chloride-free soap solution on all connections

and joints. If you see bubbles, you have a leak. Mark

these locations.

6. Use the gauge manifold to carefully release the nitro-

gen from the system. If leaks were found, repair them.

After repair, repeat the above pressure test. If no leaks

exist, proceed to system evacuation.

Figure 2

LIQUID LINE

SERVICE VALVE

VAPOR LINE

SERVICE VALVE

LIQUID LINE

SERVICE VALVE

VAPOR LINE

SERVICE VALVE

Summary of Contents for REMOTE HEAT PUMP

Page 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Page 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Page 3: ...nce and service If possible discuss unit location with the owner before proceeding This unit is for outdoor installation only It cannot be completely enclosed Refer to Figure 1 for clearances from the...

Page 4: ...Avoid burying refrigerant lines If you must bury them first dig the trench so it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separatel...

Page 5: ...Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all refrigerants must BY LAW be reclaimed If an indoor leak is suspected thoroughly ventilate the area before...

Page 6: ...a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge mani fold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach...

Page 7: ...ylinder 6 Evacuate the system to about 29 inches Hg as mea sured by the compound low side gauge 7 Open the valve to the thermocouple vacuum gauge Evacuate until the gauge reads 250 microns or less 8 C...

Page 8: ...e drop to a maxi mum of 2 from the main breaker or fuse panel to the outdoor unit A thermostat is required 1 To connect the unit to the power supply route the power supply and ground wires through the...

Page 9: ...compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding additional refrigerant to a system add only...

Page 10: ...chart shows a superheat of 20 F is ideal for these conditions Since our superheat is 30 20 10 F higher than ideal charge must be added If the system is performing properly reinstall the service port c...

Page 11: ...fter servicing is completed disconnect the power move the Defrost Time Select Tab back to 30 60 or 90 remove jumper wire on DFS and reconnect the power NOTES 1 If the time select tab remains in TEST p...

Page 12: ...ITE GREEN TYPICAL H P ROOM THERMOSTAT SYSTEM COMPOSITE DIAGRAM 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R INDOOR UNIT R RED 2 1 OT 1 OT 2 3 EHR 1 2...

Page 13: ...14 Does the compressor sound normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do c...

Page 14: ...14 2003 2004 Goodman Company L P August 2004...

Reviews: