Diagnostic Chart
LED Indications:  Flash Codes 

LED Activity

Description

Color

Comments

OFF No LED Activity

No 24 VAC

Power to control

Red, Amber, Green

Power -up verification of LED

Steady ON

Control Fault Detected Hard 

Lock

RED

Rapid Flash

Reversed Line Voltage Polarity

RED

No CFH required.

1 Flash

System Lockout - Retries 

Exceeded

RED

Retries are defined as failed ignition attempts, 

i.e. no flame sense during the trial for ignition 

period.  Recycles are defined as loss of flame 

after flame has been established during the 

trial for ignition period, and there is no limit to 

the number of recycles.

2 Flashes

Pressure Sensor Null Error:  

Inconsistent reading with 

inducer off

RED

Control waits 5 seconds after CFH before 

displaying fault.  Fault is displayed until fault 

condition corrects or CFH is removed.

3 Flashes

Pressure Sensor Span Error:  

Inconsistent reading with 

inducer on

RED

Span test maximum duration is 90 seconds.  

Once the span test fails, the control continues 

to attempt to start furnace and fault is 

displayed until fault condition corrects or CFH 

is removed.

4 Flashes

High Limit Switch Open

RED

When an open limit is detected, the control 

energizes the blower at cooling speed and the 

inducer at the RUN setting - no CFH required.  

Once the limit closes and the CFH is present, 

the furnace returns to normal operation.  Three 

limit events in a single CFH results in a 1 hour 

lockout.

5 Flashes

Flame Present with

Gas Valve OFF

RED

When detected, the control energizes the 

inducer at the "Run" setting, energize the 

blower on Heat speed, and displays fault - no 

CFH required.  Control continues normal 

operation when fault condition is corrected.

6 Flashes

Auxiliary Limit Open

RED

When detected, the control energizes the 

inducer a maximum speed, the blower at 

cooling speed and displays fault - no CFH 

required.  Control continues normal operation 

when fault condition is corrected.

7 Flashes

Gas Valve Circuit Shorted

RED

Voltage sensed at the gas valve terminal with 

the safety relay in the de-energized state.  The 

inducer is energized to maximum speed.

Lockout Notes

Power cycle will

reset all

lockout timers

N/A

N/A

Continuous Reset Cycle Power 

30 seconds

5 minute lockout

5 minute lockout

Operation continues after fault 

correction

1 Hour Fixed

5 second lockout Unlimited 

Retries

5 minute lockout Unlimited 

Retries

5 minute lockout

1 hour lockout after three 

faults in a single CFH

5 minute lockout

Summary of Contents for MES96 U Series

Page 1: ...R SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE...

Page 2: ...Air Opening Upflow Models 24 Filters Read This Section Before Installing The Return Air Duct work 24 Upright Installations 25 Horizontal Installations 25 Drain Trap Priming 25 Furnace Operation 25 Ga...

Page 3: ...me trap at time of installation may have a negative effect on combustion quality and pressure switch action WARNING FIRE OR EXPLOSION HAZARD Failue to follow safety warnings exactly could re sult in s...

Page 4: ...d other discounts or reductions Copy of the inspection report issued by carrier s representative at the time damage is reported to carrier Electrostatic Discharge ESD Precautions NOTE Discharge your b...

Page 5: ...n instructions provided and per local and national codes It must be installed indoors in a building constructed on site It must be part of a ducted system and not used in a free air delivery applicati...

Page 6: ...eater POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAIN...

Page 7: ...Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizon tal pitch as required by the National Fuel Gas Code ANSI Z223 1 instructions Determine that ther...

Page 8: ...ization can cause back drafting or improper combustion of gas fired appliances thereby exposing building occupantstogascombustionproductsthatcouldincludecarbon monoxide If this furnace is to be instal...

Page 9: ...en marche alors que tous les autres appareils raccord s au syst me de ventila tion ne sont pas en marche 1 Sceller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst me d...

Page 10: ...onally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Condensate Drain Trap and Lines for further details If the drain trap and drain line...

Page 11: ...A masonry chimney may be used as a chase or passage way for approved venting materials providing the masonry chimney is not also being used to vent products of combustion Never common vent this appli...

Page 12: ...Lengths shown in table 3 apply to single pipe two pipe installations In a two pipe installation do not add intake and vent pipe lengths together Both pipes would normally be equal in length if differ...

Page 13: ...ng the horizontal alternate vent configuration you must use the RF000142 vent drain kit See Figures 10 11 follow steps below NOTE In the horizontal left installation position a means of condensate col...

Page 14: ...rect vent application must terminate at least 12 from any opening through which flue gases may enter a building door window or gravity air inlet The vent termination of vent pipe run vertically throug...

Page 15: ...HEIGHT DIFFERENCE 12 MIN TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL Figure 14 Vertical Termination STRAIGHT ELBOWS Figure 15 VENT FLUE TEE or 45 ELBOW TURNED DOWN or 90 ELBOW TURNED DOWN OPTIONAL 12 M...

Page 16: ...swiththeexhaustventandairintaketerminations of a single unit If more than one direct vent furnace is to be installed horizontally through a common side wall maintain the clearances as in the following...

Page 17: ...Drain Trap A condensing gas furnace achieves its high level of efficiency by extractingheatfromtheproductsofcombustiontothepointwhere condensation takes place The condensate must be collected in the f...

Page 18: ...barbed end goes in the cabinet through the hole in the left side of the cabinet and secure with two field supplied 8 self tapping screws see Figure 24 2 Locate the long drain hose 3 and cut at B line...

Page 19: ...rip leg port must be sealed to prevent flue gases from escaping Insert the rubber plug removed in step 6 into the unused elbow drain port Inserting a blunt tool such as a 3 16 Allen wrench into the ce...

Page 20: ...ctrical circuit containing prop erly sized wire and fuse or circuit breaker The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating...

Page 21: ...ERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY...

Page 22: ...rning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Maximum torque for the gas valve connection is 375 in lbs excessive over tightening may damage the...

Page 23: ...ressures in excess of psig 3 48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressure...

Page 24: ...e cor ners of the opening cut the sheet metal along the scribe lines to free the duct flanges Using the scribe line along the duct flange as a guide unfold the duct flanges around the perimeter of the...

Page 25: ...MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING Furnace Startup 1 Closethemanualgasshutoffvalveexternaltothefurnace 2 Turn off the electrical powe...

Page 26: ...ure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer Reinstall plug and tighten as needed before turni...

Page 27: ...essure cannot vary by more than 0 2 w c for Natural gas from the specified setting Consult your local gas supplier if additional input rate adjustment is required 4 Turn ON gas to and relight all othe...

Page 28: ...ule performs internal checks LED will flash once at power up then remain on Integrated control module monitors safety circuits continuously Furnace awaits call from thermostat Heating Mode The normal...

Page 29: ...osed electrically auto reset sensor This switch guards against the burner flames not being properly drawn into the heat exchanger Pressure Switches The pressure switches are normally open closed durin...

Page 30: ...ol will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Field Test Mode Function When the SW1 button is pressed and held until the LED is blinking in AMBER more t...

Page 31: ...ly Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as nece...

Page 32: ...Open RED When an open limit is detected the control energizes the blower at cooling speed and the inducer at the RUN setting no CFH required Once the limit closes and the CFH is present the furnace r...

Page 33: ...Press and hold the SW1 button for more than 5 seconds results in the display of this mode Releasing the Button during this indication will cause the Error History to be cleared The button must be rel...

Page 34: ...CFM Rise CFM CFM CFM Red High Cool 3 1350 NA 1310 NA 1273 NA 1234 NA 1198 NA 1156 1117 1078 Blue Med Hi Heat 2 5 1247 29 1212 30 1167 31 1129 32 1087 33 1043 997 952 Brown Med Low 2 1151 31 1107 32 1...

Page 35: ...ore servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring d...

Page 36: ...a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminsh their warranty rights Fo...

Reviews: