the 45º section. Insert hose #2 from outside the cabinet 

through the cabinet drain hole nearest the top, secure 

it to the barbed fitting in the elbow with a red clamp.

6.  Draining the Collector Box: Install the non-grommet 

end of hose #11 from outside the cabinet in the bottom 

drain hole.  Install on collector box and secure with a 

silver clamp.

7.  Use two silver clamps and secure the hoses to drain 

trap. The  trap  outlet  faces  the  front  of  the  furnace. 

Secure the trap to the cabinet using two screws 

removed in step 2 by inserting the two screws through 

the large set of holes in the top mounting tabs of the 

trap  into  the  two  predrilled  holes  in  the  side  of  the 

cabinet. 

8.  Refer to Field Supplied Drain section for instructions 

on field supplied/installed drain on outlet of furnace 

trap.

Hose #6

Hose #5

Hose #11

Front Cover

Pressure Switch

Tube Location

Figure 26

Upflow  Model Installed Horizontally 

with Left Side Down

Minimum 5 

½

” clearance is required for the drain trap beneath 

the furnace.
*See Front Cover Pressure Switch Tube Location on Figure 

26.

1.  Remove the clamps from the two drain tubes on the trap.  

2.  Remove  the  two  screws  holding  the  drain  trap  to  the 

blower deck.

3.  Remove the trap and hoses from the blower deck.

4.  Remove the two plugs from the left side of the cabinet 

and install them in the blower deck.

5.  Draining the Vent Elbow: Locate hose #6. Measuring 

from the non-grommet end; cut off and discard 1 ½

” 

for a “D” width cabinet, 5” for a “C” width cabinet, 8 ½

” 

for a “B” width cabinet.

6.  Remove the rubber plug from vent – drain elbow side 

port. Place hose #6 on the vent – drain elbow side port 

and secure with a silver clamp .

7. 

Unused  vent-drain  elbow  drip  leg  port  must  be 

sealed to prevent flue gases from escaping. Insert 

the rubber plug removed in step 6 into the unused 

elbow drain port. Inserting a blunt tool such as a 

3/16’’ Allen wrench into the center of the rubber plug 

will stretch the plug and allow complete insertion.

8.  Locate hose #5 and cut 3

” 

 from the non-grommet end. 

Discard the section without the grommet. 

9.  Insert the cut end of tube #5 through the lower cabinet 

drain hole.

10. Connect hose #6 & hose #5 using 100º elbow and secure 

with two red clamps 

11. Draining the Collector Box: Remove cap from left side 

collector box drain port (bottom in horizontal left position) 

and install it on right side (top) collector box drain port.

12. Install the non-grommet end of hose #11 from outside 

the cabinet in the upper drain hole. Install on collector 

box and secure with a silver clamp.

13. Use two silver clamps and secure the hoses to drain trap. 

The trap outlet faces the front of the furnace. Secure the 

trap to the cabinet using two screws removed in step 2 by 

inserting the two screws through the large set of holes in 

the top mounting tabs of the trap into the two pre-drilled 

holes in the side of the cabinet.

14. Refer to Field Supplied Drain section for instructions on 

field supplied/installed drain on outlet of furnace trap.

Insert flange.  Cut 2 ½” long

.

RF000142

2 ½”

Figure 27

Upflow  Model Installed Horizontally 

With Left Side Down - Alternate

*See  Front  Cover  Pressure  Switch  Tube  Location  on 

Figure 26.

1.  Draining  the  RF000142  Coupling:  Locate  hose  #2 

(factory installed). Cut off and discard the 45° radius 

end.

2.  Install 90°radius end of hose #2 on RF000142 drain 

outlet and secure with a red clamp.

3.   Insert coupling in hose #2 and secure with a red clamp.

4.  Locate hose #5 and cut 3” from the non-grommet end. 

Discard the section without the grommet.

5.  Insert the cut end of tube #5 through the lower cabinet 

Summary of Contents for MES96 U Series

Page 1: ...R SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE...

Page 2: ...Air Opening Upflow Models 24 Filters Read This Section Before Installing The Return Air Duct work 24 Upright Installations 25 Horizontal Installations 25 Drain Trap Priming 25 Furnace Operation 25 Ga...

Page 3: ...me trap at time of installation may have a negative effect on combustion quality and pressure switch action WARNING FIRE OR EXPLOSION HAZARD Failue to follow safety warnings exactly could re sult in s...

Page 4: ...d other discounts or reductions Copy of the inspection report issued by carrier s representative at the time damage is reported to carrier Electrostatic Discharge ESD Precautions NOTE Discharge your b...

Page 5: ...n instructions provided and per local and national codes It must be installed indoors in a building constructed on site It must be part of a ducted system and not used in a free air delivery applicati...

Page 6: ...eater POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAIN...

Page 7: ...Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizon tal pitch as required by the National Fuel Gas Code ANSI Z223 1 instructions Determine that ther...

Page 8: ...ization can cause back drafting or improper combustion of gas fired appliances thereby exposing building occupantstogascombustionproductsthatcouldincludecarbon monoxide If this furnace is to be instal...

Page 9: ...en marche alors que tous les autres appareils raccord s au syst me de ventila tion ne sont pas en marche 1 Sceller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst me d...

Page 10: ...onally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Condensate Drain Trap and Lines for further details If the drain trap and drain line...

Page 11: ...A masonry chimney may be used as a chase or passage way for approved venting materials providing the masonry chimney is not also being used to vent products of combustion Never common vent this appli...

Page 12: ...Lengths shown in table 3 apply to single pipe two pipe installations In a two pipe installation do not add intake and vent pipe lengths together Both pipes would normally be equal in length if differ...

Page 13: ...ng the horizontal alternate vent configuration you must use the RF000142 vent drain kit See Figures 10 11 follow steps below NOTE In the horizontal left installation position a means of condensate col...

Page 14: ...rect vent application must terminate at least 12 from any opening through which flue gases may enter a building door window or gravity air inlet The vent termination of vent pipe run vertically throug...

Page 15: ...HEIGHT DIFFERENCE 12 MIN TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL Figure 14 Vertical Termination STRAIGHT ELBOWS Figure 15 VENT FLUE TEE or 45 ELBOW TURNED DOWN or 90 ELBOW TURNED DOWN OPTIONAL 12 M...

Page 16: ...swiththeexhaustventandairintaketerminations of a single unit If more than one direct vent furnace is to be installed horizontally through a common side wall maintain the clearances as in the following...

Page 17: ...Drain Trap A condensing gas furnace achieves its high level of efficiency by extractingheatfromtheproductsofcombustiontothepointwhere condensation takes place The condensate must be collected in the f...

Page 18: ...barbed end goes in the cabinet through the hole in the left side of the cabinet and secure with two field supplied 8 self tapping screws see Figure 24 2 Locate the long drain hose 3 and cut at B line...

Page 19: ...rip leg port must be sealed to prevent flue gases from escaping Insert the rubber plug removed in step 6 into the unused elbow drain port Inserting a blunt tool such as a 3 16 Allen wrench into the ce...

Page 20: ...ctrical circuit containing prop erly sized wire and fuse or circuit breaker The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating...

Page 21: ...ERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY...

Page 22: ...rning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Maximum torque for the gas valve connection is 375 in lbs excessive over tightening may damage the...

Page 23: ...ressures in excess of psig 3 48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressure...

Page 24: ...e cor ners of the opening cut the sheet metal along the scribe lines to free the duct flanges Using the scribe line along the duct flange as a guide unfold the duct flanges around the perimeter of the...

Page 25: ...MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING Furnace Startup 1 Closethemanualgasshutoffvalveexternaltothefurnace 2 Turn off the electrical powe...

Page 26: ...ure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer Reinstall plug and tighten as needed before turni...

Page 27: ...essure cannot vary by more than 0 2 w c for Natural gas from the specified setting Consult your local gas supplier if additional input rate adjustment is required 4 Turn ON gas to and relight all othe...

Page 28: ...ule performs internal checks LED will flash once at power up then remain on Integrated control module monitors safety circuits continuously Furnace awaits call from thermostat Heating Mode The normal...

Page 29: ...osed electrically auto reset sensor This switch guards against the burner flames not being properly drawn into the heat exchanger Pressure Switches The pressure switches are normally open closed durin...

Page 30: ...ol will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Field Test Mode Function When the SW1 button is pressed and held until the LED is blinking in AMBER more t...

Page 31: ...ly Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as nece...

Page 32: ...Open RED When an open limit is detected the control energizes the blower at cooling speed and the inducer at the RUN setting no CFH required Once the limit closes and the CFH is present the furnace r...

Page 33: ...Press and hold the SW1 button for more than 5 seconds results in the display of this mode Releasing the Button during this indication will cause the Error History to be cleared The button must be rel...

Page 34: ...CFM Rise CFM CFM CFM Red High Cool 3 1350 NA 1310 NA 1273 NA 1234 NA 1198 NA 1156 1117 1078 Blue Med Hi Heat 2 5 1247 29 1212 30 1167 31 1129 32 1087 33 1043 997 952 Brown Med Low 2 1151 31 1107 32 1...

Page 35: ...ore servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring d...

Page 36: ...a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminsh their warranty rights Fo...

Reviews: