background image

23

 A semi-rigid connector to the gas piping can be used outside 

the cabinet per local codes. From the elbow, the length of pipe 

and the fittings required will vary by the side chosen, location 

of union and cabinet width.  The union may be placed inside 

or outside of the cabinets.

Alternate

Gas Line

Location

Plug in

Alternate

Gas Line

Hole

* Ground

Joint

Pipe

Union

Gas Valve

*Ground

Joint

Pipe

Union

Manual Shut Off Valve

(upstream from

ground joint

pipe union)

Grommet

in Standard

Gas Line

Hole

Drip Leg

Burner

Manifold

* NOTE: Union may be inside furnace cabinet where allowed by local codes.

UPFLOW

Figure 29

Manual Shut Off Valve

           (upstream from

           ground joint pipe union)

Drip Leg

Plug in Alternate Gas Line Hole

Grommet in

Standard Gas Line Hole

Alternate

Union

Location

Burner

Drain Trap

Gas Valve

Plug in Main Gas Line Hole

Manifold

UPFLOW - HORIZONTAL LEFT

Figure 30

Gas Piping Checks

Before placing unit in operation, leak test the unit and gas con

-

nections.
Check for leaks using an approved chloride-free soap and 

water solution, an electronic combustible gas detector, or other 

approved testing methods.

NOTE:

  Never exceed specified pressures for testing.  Higher 

pressure may damage the gas valve and cause subsequent 

overfiring, resulting in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping 

system before pressure testing the supply piping system with 

pressures in excess of  ½

 

psig (3.48 kPa).

Isolate this unit from the gas supply piping system by closing 

its external manual gas shutoff valve before pressure testing 

supply piping system with test pressures equal to or less than  

½

 

 psig (3.48 kPA).

Circulating Air & Filters

Duct work - Air Flow

Duct systems and register sizes must be properly designed 

for the CFM and external static pressure rat ing of the furnace. 

Ductwork should be designed in accor dance with the rec

-

ommended  methods  of    “Air  Conditioning  Contractors  of 

America” Manual D.
Install the duct system in accordance with Standards of the 

National Board of Fire Underwriters for the Installation of Air 

Conditioning,  Warm Air  Heating  and  Ventilating  Systems. 

Pamphlets No. 90A and 90B.

.



Figure 31

A closed return duct system must be used, with the return duct 

connected to the furnace. 

NOTE:

 

 Ductwork must never be 

attached to the back of the furnace.

 

 For upflow installations 

requiring 1800 CFM or more, use either two side returns or 

bottom return or a combination of side/bottom. Flexible joints 

may be used for supply and return con nections to reduce 

noise transmission. To prevent the blower from inter fering 

with combustion air or draft when a central return is used, a 

connecting duct must be installed between the unit and the 

utility room wall.  Never use a room, closet, or alcove as a 

return air chamber.

Checking Duct Static

E

DGES

 

OF

 

SHEET

 

METAL

 

HOLES

 

MAY

 

BE

 

SHARP

. U

SE

 

GLOVES

 

AS

 

A

 

PRECAUTION

 

WHEN

 

REMOVING

 

SHEET

 

METAL

 

FROM

 

RETURN

 

AIR

 

OPENINGS

.

WARNING

Refer  to  your  furnace  rating  plate  for  the  maximum  ESP 

(external duct static) rating.

Summary of Contents for MES96 U Series

Page 1: ...R SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE...

Page 2: ...Air Opening Upflow Models 24 Filters Read This Section Before Installing The Return Air Duct work 24 Upright Installations 25 Horizontal Installations 25 Drain Trap Priming 25 Furnace Operation 25 Ga...

Page 3: ...me trap at time of installation may have a negative effect on combustion quality and pressure switch action WARNING FIRE OR EXPLOSION HAZARD Failue to follow safety warnings exactly could re sult in s...

Page 4: ...d other discounts or reductions Copy of the inspection report issued by carrier s representative at the time damage is reported to carrier Electrostatic Discharge ESD Precautions NOTE Discharge your b...

Page 5: ...n instructions provided and per local and national codes It must be installed indoors in a building constructed on site It must be part of a ducted system and not used in a free air delivery applicati...

Page 6: ...eater POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAIN...

Page 7: ...Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizon tal pitch as required by the National Fuel Gas Code ANSI Z223 1 instructions Determine that ther...

Page 8: ...ization can cause back drafting or improper combustion of gas fired appliances thereby exposing building occupantstogascombustionproductsthatcouldincludecarbon monoxide If this furnace is to be instal...

Page 9: ...en marche alors que tous les autres appareils raccord s au syst me de ventila tion ne sont pas en marche 1 Sceller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst me d...

Page 10: ...onally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Condensate Drain Trap and Lines for further details If the drain trap and drain line...

Page 11: ...A masonry chimney may be used as a chase or passage way for approved venting materials providing the masonry chimney is not also being used to vent products of combustion Never common vent this appli...

Page 12: ...Lengths shown in table 3 apply to single pipe two pipe installations In a two pipe installation do not add intake and vent pipe lengths together Both pipes would normally be equal in length if differ...

Page 13: ...ng the horizontal alternate vent configuration you must use the RF000142 vent drain kit See Figures 10 11 follow steps below NOTE In the horizontal left installation position a means of condensate col...

Page 14: ...rect vent application must terminate at least 12 from any opening through which flue gases may enter a building door window or gravity air inlet The vent termination of vent pipe run vertically throug...

Page 15: ...HEIGHT DIFFERENCE 12 MIN TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL Figure 14 Vertical Termination STRAIGHT ELBOWS Figure 15 VENT FLUE TEE or 45 ELBOW TURNED DOWN or 90 ELBOW TURNED DOWN OPTIONAL 12 M...

Page 16: ...swiththeexhaustventandairintaketerminations of a single unit If more than one direct vent furnace is to be installed horizontally through a common side wall maintain the clearances as in the following...

Page 17: ...Drain Trap A condensing gas furnace achieves its high level of efficiency by extractingheatfromtheproductsofcombustiontothepointwhere condensation takes place The condensate must be collected in the f...

Page 18: ...barbed end goes in the cabinet through the hole in the left side of the cabinet and secure with two field supplied 8 self tapping screws see Figure 24 2 Locate the long drain hose 3 and cut at B line...

Page 19: ...rip leg port must be sealed to prevent flue gases from escaping Insert the rubber plug removed in step 6 into the unused elbow drain port Inserting a blunt tool such as a 3 16 Allen wrench into the ce...

Page 20: ...ctrical circuit containing prop erly sized wire and fuse or circuit breaker The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating...

Page 21: ...ERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY...

Page 22: ...rning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Maximum torque for the gas valve connection is 375 in lbs excessive over tightening may damage the...

Page 23: ...ressures in excess of psig 3 48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressure...

Page 24: ...e cor ners of the opening cut the sheet metal along the scribe lines to free the duct flanges Using the scribe line along the duct flange as a guide unfold the duct flanges around the perimeter of the...

Page 25: ...MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING Furnace Startup 1 Closethemanualgasshutoffvalveexternaltothefurnace 2 Turn off the electrical powe...

Page 26: ...ure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer Reinstall plug and tighten as needed before turni...

Page 27: ...essure cannot vary by more than 0 2 w c for Natural gas from the specified setting Consult your local gas supplier if additional input rate adjustment is required 4 Turn ON gas to and relight all othe...

Page 28: ...ule performs internal checks LED will flash once at power up then remain on Integrated control module monitors safety circuits continuously Furnace awaits call from thermostat Heating Mode The normal...

Page 29: ...osed electrically auto reset sensor This switch guards against the burner flames not being properly drawn into the heat exchanger Pressure Switches The pressure switches are normally open closed durin...

Page 30: ...ol will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Field Test Mode Function When the SW1 button is pressed and held until the LED is blinking in AMBER more t...

Page 31: ...ly Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as nece...

Page 32: ...Open RED When an open limit is detected the control energizes the blower at cooling speed and the inducer at the RUN setting no CFH required Once the limit closes and the CFH is present the furnace r...

Page 33: ...Press and hold the SW1 button for more than 5 seconds results in the display of this mode Releasing the Button during this indication will cause the Error History to be cleared The button must be rel...

Page 34: ...CFM Rise CFM CFM CFM Red High Cool 3 1350 NA 1310 NA 1273 NA 1234 NA 1198 NA 1156 1117 1078 Blue Med Hi Heat 2 5 1247 29 1212 30 1167 31 1129 32 1087 33 1043 997 952 Brown Med Low 2 1151 31 1107 32 1...

Page 35: ...ore servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring d...

Page 36: ...a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminsh their warranty rights Fo...

Reviews: