![AMALGAMATED INSTRUMENT LD5-RS Operation And Instruction Manual Download Page 56](http://html1.mh-extra.com/html/amalgamated-instrument/ld5-rs/ld5-rs_operation-and-instruction-manual_2915959056.webp)
OFF
- calculated channel not used.
Hi
- calculated channel shows the highest positive value from all of the selected input channels.
Lo
- calculated channel shows the lowest value from all of the selected input channels.
dIFF
- calculated channel shows the difference in value between the highest and lowest selected input channel
readings.
AUg
- calculated channel shows the average of all selected input channel readings.
d.AUg
- calculated channel shows a value equal to the highest positive or negative value and the average of the
selected channels.
P.AUg
- calculated channel shows a value equal to the highest positive value and the average of the selected
channels.
N.AUg
- calculated channel shows a value equal to the average minus the lowest value of the selected channels.
S.dIFF
- calculated channel shows the difference (positive or negative) between the first two selected active
channels.
Add
- calculated channel shows the arithmetic sum of all the selected channels.
PC 1
- calculated channel shows the percentage of the first selected channel to the sum of all selected channels
including itself.
PC 1
- calculated channel shows the percentage of the second selected channel to the sum of all selected channels
including itself.
Sub
- subtraction, channel 2 will be subtracted from channel 1 and if there are more than 2 channels the next
channel will be subtracted from the result of channel 1 minus channel 2 etc.
Prod
- multiplication, channel 1 and 2 will be multiplied and if there are more than 2 channels the result of channel
1 times channel 2 will be multiplied by the next channel etc.
diu
- division. channel 1 divided by channel 2 and if there are more than 2 channels this result will be divided by
the next channel etc.
SinE
- sine, channel 1 is multiplied by the sine of the value on channel 2 and if there are more than 2 channels
this result will be multiplied by the sine of the value of the next channel etc.
CoS
- cosine, channel 1 is multiplied by the cosine of the value on channel 2 and if there are more than 2 channels
this result will be multiplied by the cosine of the value of the next channel etc.
R.AUG
- rolling average. The rolling average causes the display to show the rolling average. The rolling average
will take the current input and average this with the previously calculated average figure. The rolling and fixed
averages both use the count set by the
A.cnt
function to set the number of input values to be averaged but the
rolling average updates with every new input value received.
F.AUG
- fixed average. The fixed average causes the display to show the average of the number of data strings
selected at the
A.cnt
function. The fixed average will only be displayed at the end of the number of data string
selected. For example if
A.cnt
is set to
20
then the display will update when 20 data strings have been input and
averaged (assuming timeouts have not been exceeded).
Example 1: To program calculated channel 1 to activate relay 1 and 2 to operate on an highest value if the value of
any of the 8 inputs exceeds 120 the basic settings are:
•
At the
CONF CHAN Cnt
function ensure that at least one calculation channel is set
•
Set
AL1 High
to
120
•
Set
AL1 RLYS
to
RLY1 On
and
RLY2 On
•
Set
AL1 OPEr
to
Hi.Lo
•
Set
AL1 Ch
to
CC1
•
Set
CC1 Func
to
Hi
•
Set
CC1 ChAn SEL
to
Ch1 On
,
Ch2 On
,
Ch3 On
,
Ch4 On
,
Ch5 On
,
Ch6 On
,
Ch7 On
and
Ch8
On
Relays 1 and 2 will now activate if any of the 8 inputs exceeds a value of 120 and if annunciators are fitted annun-
ciator 1 will flash. In the example above if
AL1 Lo
had been set to
120
with the high alarm set to
OFF
then the
relays would activate if any of the inputs falls below 120.
56 of