5.54
Decimal point
Section:
IN 1
Display:
d.Pnt
Range:
0
,
0.1
,
0.02
,
0.003
Default Value:
0
Default Access Level
CAL
Function number
4100
Displays and sets the decimal point. By pressing the
^
or
v
pushbutton at the
dCPt
function the decimal point
position may be set. The display will indicate as follows:
0
(no decimal point),
0.1
(1 decimal place),
0.02
(2
decimal places) or
0.003
(3 decimal places). Note if the decimal point is altered the display alarm settings etc.
will need to be re-adjusted checked. The
Auto
selection is used when
CodE
function is set to
ind131
only.
In this mode the panel meter expect to receive a separate data word which contains the decimal point position, the
panel meter then automatically adjusts the decimal points displayed to match.
5.55
Display rounding
Section:
IN 1
Display:
d.rnd
Range:
1
to
5000
Default Value:
1
Default Access Level
CAL
Function number
43b0
Displays and sets the display rounding value. This value may be set to 1 - 5000 displayed units. Display rounding
is useful for reducing the instrument resolution without loss of accuracy in applications where it is undesirable to
display to a fine tolerance. To set the display rounding value go to the
drnd
function and use the
^
or
v
push
buttons to set the required value then press
F
to accept this selection.
5.56
Digital filter
Section:
IN 1
Display:
FLtR
Range:
0
,
1
,
2
,
3
,
4
,
5
,
6
,
7
,
8
Default Value:
0
Default Access Level
CAL
Function number
43C0
Displays and sets the digital filter value. Digital filtering uses a weighted average method of determining the
display value and is used for reducing display value variation due to short term interference. The digital filter range
is selectable from
0
to
8
, where
0
= none and
8
= most filtering. Use
^
or
v
at the
FLtr
function to alter the
filter level if required. Note that the higher the filter setting the longer the display may take to reach its final value
when the input is changed, similarly the relay operation and any output options will be slowed down when the filter
setting is increased. To set the digital filter value go to the
FLtr
function and use the
^
or
v
push buttons to set
the required value then press
F
to accept this selection.
48 of