LEVIGATO DRIVES (LG SERIES)
|
LEVIGATO ANTRIEBE (SERIE LG)
|
COMMANDES LEVIGATO (SERIE LG)
28
ADjUSTMENT
MENU
SETTING
DESCRIPTION
VALUES
DEfAULT
VALUE
P3
f2
Manual mode
. Control is performed by means
of holding the control button in the pressed
state (buttons
or
and drive
connection ‘
SBS
’ output). The remote control
commands are not executed. Connected security
devices are activated. The manual mode disables
the automatic mode
no
—
Off
/
on
—
ON
no.
P4
f1
Pause time until automatic closing
from any
position except pedestrian
no
—
Off
/
00
,
01
…
99
00
—0 sec;
99
—99 secs
no.
f2
Pause time until automatic closing
from any
position except pedestrian after photocells
activation (the input connection ‘
PH1
’)
no.
f3
Pause time until automatic closing
from
the pedestrian position. It is performed if the
pedestrian position have been set (setting
P1
–
f2
)
no.
f4
Pause time until automatic closing
from any
position except pedestrian after photocells
activation (the input connection ‘
PH1
’). It is
performed if the pedestrian position have been
set (setting
P1
–
f2
)
no.
Y
If automatic closing is enabled (pause time is set), the
PHOTOTEST
function (
P7
-
f3
-on setting) will
be automatically enabled and the
PH1
connection input will only be active when closing (
P7
-
f1
-
CL
setting). The connection of photocells is obligatory according to
fig. 26
(EN 12453 device type
D
)
P5
f1
Drive force when opening.
When opening,
the detection of foreign object by the drive will
result in an immediate stop of movement
ATTENTION!
Force and speed
settings are made by the manu-
facturer. The factory settings of
force and speed ensure compli-
ance with the requirements of the
safety standard (EN 12453 type
C
of built-in device) for a certain
type of ALUTECH doors with the
permissible limit parameters (sec-
tion 2.2. ‘Technical parameters’).
In other cases, a specialist must
check the compliance with the
requirements of the standard
(EN 12453) or the another type of
safety device (EN 12453 type
E
)
should be applied.
f2
Drive force when closing.
When closing, the
detection of foreign object by the drive will
result in an immediate stop of movement and in
subsequent full opening
P6
f1
Speed of door movement when opening.
The
maximum speed is set at the factory settings of
the drive
f2
Speed of door movement when closing
. At
the factory settings of the drive, the speed of the
doors when closing is ~20% less than the speed
when opening
f3
Time of smooth door acceleration at the
beginning of opening
f4
Delay time of door movement before the final
position of opening
f5
Time of smooth door acceleration at the
beginning of closing
f6
Delay time of door movement before the final
position of closing
Y
The setting and adjustment of the force and speed should be carried out by qualified personnel
(EN 12635) of the competent organization. Settings should ensure safe and correct operation of the doors
in accordance with applicable regulations (EN 12453), excluding damage and false positives. The user is
blocked from entering the
P5
and
P6
menu