CONTROL UNITS СU-TR230 / СU-TR400
107
107
SETTINGS
MENU
SETTING
DESCRIPTION
VALUES
FACTORY
VALUE
P5
Y
The height from the floor, after which the operation of the
SE
input is disabled should be
less than 50 mm. After setting the edge disabling and any change (setting) in the end po-
sition of the closed doors, it is necessary to verify to confirm compliance with the require-
ments of the safety standard (EN 12453). An object 50 mm high located on the floor should
be detected by contact with the lower edge of the door leaf (the doors will stop and open).
It is verified in the middle and at the edges of the door leaf
F8
*
Slow speed at the start of closing
no
— disabled
01
,
02
…
05
:
01
— 1 s
05
— 5 s
no.
F9
*
Slow speed near the floor.
When the setting is
enabled the position of slow speed starting is
set in the same way as for setting
P5
–
F7
(the
starting position of the settings is the same)
no
— disabled
on
— enabled
no.
Y
ATTENTION!
When the setting is on, please check up that the door stops in the required
end positions (section 6.1, point 4)
P7
F3
PHOTOTEST function.
When the setting is on,
before starting the movement, an automatic
verification of the operation of the photocells
connected to the input
PH1
is performed
(
Table
2, connector 20).
Figure
s 16–18 — Examples of connection
diagrams of safety devices to input
PH1
for
performing an automatic verification
no
— disabled
on
— enabled
no.
Y
The
PHOTOTEST
function cannot be disabled (
no
) if automatic closing is enabled
(pause time is set in the settings of menu
P4
)
F4
Safety edge
(input
SE
,
Table
2, connector 20).
The type of safety edge is set: resistive edge
(8.2 kOhm) or optoelectronic edge (OSE)
01
— 8,2 kOhm /
02
— OSE (optosensors)
01.
F5
Input
A
operation
(
Table
2, connector 20).
The control input is operated either in the
open direction or in the close direction. Also
doors can be opened at required (set) height
(intermediate opening position)
OP
— opening direction
CL
— closing direction
AL
— opening at set
height (c. 6.6)
OP.
P8
F2
The delay time of the beginning of
movement
(time of preliminary operation of
the light indication). During the countdown
of the delay time, the signal lamp will be
operated, the traffic light will be red, signaling
the upcoming start of movement
no
— disabled
01
,
02
…
10
:
01
— 1 s
10
— 10 s
no.
F3
Lighting operating time after stopping the
movement.
The operating time of the lighting
lamp is set if the outputs of connectors
7
–
9
are
set appropriately (value
02
,
Table
14).
00
,
01
…
99:
00
— after the end of
the movement is
disabled (0 s)
01
— 10 s
99
— 990 s (16,5 min)
00.
Y
During movement and during the delay time of the beginning of movement
(setting
P8
–
F2
) it is impossible to turn off the light lamp using the command of the radio
remote control (the value of the LIGHTING OFF command,
Table
4)