6. HX3040 Redundancy
306
The Table 6-6 shows all messages to be presented to the states and changes of redundancy, accessible
to the user by means of diagnosis "DG_HX3040_01. RedDgnLoc. RedundancyDiagnostics.
eStateChangeReason.". Messages presented in the description are identical to the messages that will
be displayed in the Log. For more information about Log, see the Redundancy Event Logs. For more
information about the redundancy states see Transition between Redundancy States.
String do Estado
State
Value
Log Message
Description
INIT_APP
0
Redundancy initialization started
Redundancy process was initiated.
INIT_DONE
1
Redundancy initialization done
Redundancy process completed.
INIT_REDUNDANT_DATA_O
VER_MAXIMUM
2
Error: Redundant data is too big
Area destined to redundancy exceeds the
maximum threshold.
INIT_CLUCONF_ERROR
3
CPU is not inserted in the right
position for a redundant setup
The CPU is not inserted in the correct position for a
redundant configuration.
NCF_LOCAL_CPU_USER_C
MD
100
User state change requested via
local diagnostic command bit
Not configured for other states, state exchange
command via diagnostic local bit.
NCF_REMOTE_CPU_USER
_CMD
101
User state change requested via
remote diagnostic command bit
Not configured for other states, state exchange
command via diagnostic remote bit.
NCF_LCD_MENU_USER_C
MD
102
User state change requested via
LCD menu
Not configured for other states, state exchange
control via LCD menu.
NCF_AUTO_CONFIGURATI
ON
103
Auto configuration
Not configured for other states, auto configuration
of redundancy.
STR_STANDBY
200
Other CPU is controlling the
system
Initializing to Standby, the other CPU is controlling
the system.
STR_ACTIVE
201
CPU started controlling the
system
Initializing to Active, CPU started controlling the
Active system.
STR_CONFIG_ERROR
202
The Application has a
configuration error
Booting to non-configured, the application has
configuration error.
STR_LINK_WITH_INTERNA
L_FAILURE
203
Redundant link with an internal
failure
Booting to Inactive, internal redundancy channel
failed.
STR_NO_COMM_OTHER_C
PU_AND_BUS_IDLE
204
This CPU is unable to
communicate with the other CPU
via redundant link and the BUS is
idle
Booting to Active, this CPU is unable to
communicate with the other CPU via redundancy
channel and the bus is stopped.
STR_NO_COMM_OTHER_C
PU_AND_BUS_BUSY
205
This CPU is unable to
communicate with the other CPU
via redundant link and the BUS is
busy
Booting to Inactive, this CPU is unable to
communicate with the other CPU via redundancy
channel and the bus is in use.
STR_INCOMPATIBLE_FIRM
WARE
206
The firmware version of this CPU
is not compatible with the other
one
Booting to Inactive, the firmware version of this
CPU is not compatible with the other one.
STR_APPLICATION_DIFF
207
The Application between the
CPUs is different
Booting to non-Configured, the application in the
CPUs are different.
STR_ARCHIVE_DIFF
208
The Project Archive between the
CPUs is different
Booting to non-Configured, the Project Archive
between CPUs is different.
STR_ONLINE_CHANGE_AP
PLY
209
There is an online change in the
Application of the Active CPU
Booting to non-Configured, an online load of the
application was performed on the Active CPU.
STR_DATA_EXCHANGE_FA
ILED
210
Redundant data synchronization
failed
Booting to Inactive, redundant data sync failed.
STR_APP_STATE_DIFF_WI
TH_OTHER_ACT
211
The application state of this CPU
is different from the other Active
CPU
Booting to non-Configured state, the application
state of this CPU is different from another Active
CPU.
STR_APP_STATE_DIFF_WI
TH_OTHER_NON_ACT
212
The application state of this CPU
is different from the other Non-
Active CPU
Booting to Active, the application state of this CPU
is different from another Inactive CPU.
STR_BUS_ERROR
213
Bus error detected
Booting to Inactive, bus error detected.
STR_OTHER_CPU_ACT_WI
TH_BRKP
214
Other CPU is Active and with
Application stopped in a
Breakpoint
Booting to Inactive, the other CPU is in Active and
with the application stop on Breakpoint.
SBY_LINK_WITH_INTERNA
L_FAILURE
301
Redundant link with an internal
failure
Standby to Active, redundancy channel with
internal failure.
SBY_APPLICATION_DIFF
302
The Application between the
CPUs is different
Standby to Non-Configured, the application in the
CPUs is different.