P210WLP Series Air Dryer User’s Guide
Page 30 of 91
P017455 – Rev. C
8.6.4
High Cabinet Temperature Alarm -
Occurs when the temperature in the cabinet rises above 120° F (49° C) for
more than ten (10) seconds. If this alarm is present for one (1) minute or
more, the Air Dryer will go into
SHUTDOWN
mode to prevent damage to
the unit.
See section 13.12 for troubleshooting information.
8.6.5
High Compressor Last Run Time Alarm –
Occurs when the compressor takes longer to pressurize the air tank than the
set point for the alarm.
See section 13.17 for troubleshooting information.
8.6.6
Compressor Total Hour Alarm –
Occurs when the compressor has reached a recommended maintenance
interval. Perform the required maintenance.
See section 10.3 for maintenance information.
8.6.7
High Duty Cycle Alarm –
Occurs when the duty cycle rises above the alarm set point. The duty cycle is
calculated based on the previous two compressor last run time values.
Summary of Contents for Puregas P210W2LP