Altec AIR, LLC
P210WLP Series Air Dryer User’s Guide
Page 32 of 91
P017455 – Rev. C
o
Set High Humidity Threshold
o
Set High Duty Cycle Threshold
o
Set Compressor Last Run
❖
Network Setup – Requires System Keyword to Access
o
Set IP Address
o
Set Subnet Mask
o
Set Gateway Address
o
Set Trap Server (1-4)
o
Change Keyword
8.7.1.3
Press the Enter (●) button to access the desired setup menu screen
8.7.2
Set Alarm Delay –
8.7.2.1
The Alarm Delay allows the dryer time to correct out of an alarm
condition on its own without signaling an alarm.
o
ON
– (default) – waits one (1) minute before signaling alarms
o
OFF
– Signals alarms immediately
8.7.2.2
From the system setup
menu screen, press the
Up (
) & Down (
)
Arrow Buttons to
navigate between the system setup options to locate “SET ALARM
DELAY”
8.7.2.3
Press the Enter (●) button to enter the change value screen
8.7.2.4
Press the Right (
) & Left (
) Arrow Buttons to toggle between
YES / NO
8.7.2.5
Press the Enter (●) button on the desired value
8.7.2.6
Press the Right (
) & Left (
) Arrow Buttons to toggle between
YES / NO. If YES is selected the new value will be saved. If NO is
selected the new value will not be saved, and the previous value will be
retained