61
6�9�10 Powering Off and On Line Power Loads
A line power load usually has multiple channels from different modules assigned to it. It may be necessary to oc-
casionally power off, then power on the load.
To power off or on a load:
1. Go to Power Systems > Line Power System > Inventory > Line Power Loads and click on the details icon for
the load to be powered off.
2. In the Status table, verify that the Channels value is at least 1. The Power On/Off buttons will only work if there
are one or more channels assigned to the load.
3. In the Configuration table, click the Power Off button. After a few moments the Channels Enabled, Total
Output Current and Total Output Power values in the Status table will go to zero. This indicates that the load
has been turned off. The Power Off button will become disabled and the Power On button becomes enabled.
4. To turn on the load, press the Power On button alarm.
6�9�11 Powering Down the Controller
Sometimes it may be necessary to power down the controller to replace, remove or repair rectifiers.
1. From the main dashboard, go to
Controller > Controller Status
and then click controller reset.
2. From the LCD screen go to
Menu > Controller > Controller Status > Reset Controller
.
3. While the controller LEDs are cycling, power down the controller by removing the power pin on the right-side
of the controller.
CAUTION!
You must use the LCD or web interface to reset the controller. This ensures that recent
changes and files are saved properly.