6�3 Tools Required
Various insulated tools are essential for product installation. The following list is a guide:
•
Phillips head screwdriver, #2 (tip size 3/16")
•
Slot head screwdriver (blade size 1/8")
•
Digital voltmeter equipped with test leads
•
Cutters, crimpers, and wire strippers 0.25 to 10mm
2
(#24 to #6 AWG)
CAUTION!
The LPS36 is suitable for connection to the Central Office (NEC)
The LPS36 must be grounded via a copper ground conductor.
Before making connections all bare grounding connection points to the LPS36 must be
cleaned and coated with an anti-oxidant solution.
Before making connections all surfaces on the LPS36 that are un-plated must be
brought to a bright finish and treated with and anti-oxidant solution.
To ensure electrical continuity, all non-conductive surfaces on the LPS36 should be
removed from all threads and all connection points.
The LPS36 utilizes a 2-hole compression lug with a #6 AWG wire that utilizes 8.8 ft-lbs
torque to secure it to the frame and LPS36.