PV Charge interface displays today’s or total
electricity quantity battery charged from the
PV-panels.
Error Logs interface displays the 10 latest fault
records of this device, including the name of
the fault and time of error.
Make sure all numbers in the information
menu are correct.
Step 8:
Click the Grid Function to set up
relevant parameters about the grid
Step 9:
Set the Max. Feed in rate value.
For example, the storage capacity is
6.6kW, the on grid capacity is 3kW,
feed-in power is limited within 5kW,
then the max. feed in rate = 5 / (6.6+3)
≈ 52%
Step 10:
Click Function-System Mode to set
system mode: DC, AC, Hybrid.
Step 11:
Click the mode then set up
work mode.(self-use or force time
charge)
Step 4:
Set on-grid capacity, storage
capacity and number of PV strings (MPPT
number).
On-grid capacity: Existing PV capacity
Storage capacity: PV capacity on SMILE5
Step 5:
Click the Battery Function and check
battery type SMILE5-BAT.
Step 6:
Check SOC Calibration function set
No.
Step 7:
Check the Battery Ready function
set No. If you only use the inverter without
battery, please set it Yes.
EMS INTRODUCTION AND SET UP
EMS INTRODUCTION AND SET UP
Step 1:
Click setting and enter the password.
The installation's password is a four-digit
password: 1111, after four-digits password was
correctly input, you can enter into the main
Setting interface (administrator permissions).
Step 2:
Click Function to enter function
setting.
Step 3:
Click Solar to set the Solar relevant
information.
4.2.4 Setting
4.2.4.1 General Setting
43