3. Operation
3-6
3.2.3 The Maximum Combined Simultaneous Power Consumption
The following chart shows the maximum power available from the 120V-20A GFCI receptacles during
simultaneous consumption (main terminals and receptacles) for both single or three phase settings. Values
shown in the left column give the maximum current available at the 120V-20A GFCI receptacles compared
to the value of the simultaneous current consumption from the main terminals.
[Allowable load capacity of GFCI at single phase]
Single Phase
(240/120V)
GFCI
Receptacle
kW
A
14.4
0
13.2
5
12.0
10
10.8
15
9.6
20
[Allowable load capacity of GFCI at three phase]
Three Phase
(240/480V)
GFCI
Receptacle
kVA
A
25.0
0
20.8
5
16.7
10
12.5
15
8.4
20
When the main terminal, single-phase (240/120V) or three-phase (240/480V) is used together with the
GFCI outlet (single-phase 120V), the above allowable load capacity of the GFCI outlet must not be
exceeded.