3. Operation
3-4
3.2.1 Output Terminal connections
Voltage can be selected with voltage selector switch.
Voltage Selector Switch
Three phase 480/277V
A040250-2
A040153-1
A040154-1
A040155-1
Voltage Selector Switch
Three phase 240/139V
A040251-2
A040156-1
A040157-1
A040158-1
Voltage Selector Switch
Single phase 240/120V
A040161-2
A040159-1
A040160-1
A040141
During operation, do not operate the voltage selector switch.
Voltage selection during operation may cause abnormal voltage
on the load side to damage the load and may cause a fire.
In addition, it could cause damage to generator and automatic
voltage regulator (AVR).
Be sure to shut off the generator before using the voltage selector
switch.
When voltage selection is completed, lock the voltage selector
switch in position to prevent anyone from operating it.