Connection of main power inlet
4
6
5
1
3
2
CFD1299N
1.
Main switch
2.
Strain relief
3.
Sag of inlet cable
4.
U, L1
5.
V, L2
6.
W, L3
Figure 31
Machine with Tilting
The selected power supply cable needs to come from above and
vertical directed downwards in line with the supply cable entry,
refer to
.
35 - 60 kg / 350 - 600 L Models
CFD1320NA
3
2
1
30cm
40cm
50cm
1.
Power supply cable
2.
Back of machine
3.
Tilting base
Figure 32
The cable needs to be on ± 11.81 in. [30 cm] backwards away
from the backside when in tilting base, or rest position. Just be-
fore entry, a sag of a minimum of 1.97 in. [5 cm] and maximum
of 5.91 in. [15 cm] must be provided.
From the point of entry, up to 39.37 in. [1 m] high, no fixation of
the supply cable is allowed.
Determining AWG Sizes
Manufacturer’s Recommended Minimal Conductor Section
Power supply protection device nominal current (US)
Min. phase conductor
section
Min. protection conduc-
tor section
Automatic circuit breakers
Fuses
16A (15A)
10A (10A)
1.5 mm
2
(AWG 15)
1.5 mm
2
(AWG 15)
20A (20A)
16A (15A)
2.5 mm
2
(AWG 13)
2.5 mm
2
(AWG 13)
25A (-)
20A (20A)
4 mm
2
(AWG 11)
4 mm
2
(AWG 11)
40A (40A)
32A (30A)
6 mm
2
(AWG 9)
6 mm
2
(AWG 9)
63A (-)
50A (50A)
10 mm
2
(AWG 7)
10 mm
2
(AWG 7)
80A
63A
16 mm
2
(AWG 5)
16 mm
2
(AWG 5)
Table 20
continues...
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
40
Part No. D2601EN