background image

(Refer to Monitoring Temperature Values).

A skilled and experienced technician must examine the heating
and air outlet system before the machine is put in operation again.

WARNING

IF FAILURE 37 OCCURS WE CAN EXPECT THERE IS
RISK OF BURN AND NECESSARY ACTIONS MUST
BE TAKEN TO REDUCE TEMPERATURE.

C143

1. Check the air outlet system. If the airflow is not sufficient,

adjust the air outlet system.

2. Check the temperature sen-
sor.

If the temperature sensor is not
measuring correctly, replace
the temperature sensor.

3. Check the heating system.

If the heating system is bro-
ken, repair or replace the heat-
ing system.

4. Check the heating contactor
(valve).

If the heating contactor (valve)
is not functional, repair or re-
place the component.

5. Check the wiring.

If the wiring is damaged, re-
pair the wiring.

6. Check the Safety Thermo-
stats ST1 & ST2.

The Safety Thermostats should
go open before failure 37 is
generated.

7. Check the output relay that
controls the heating system.

If the output relay is not func-
tional, replace the control
board.

8. Check the input Signal by
monitoring the state at the
Service menu.

If the input is not functional,
replace the control board.

 Failure 39: Error Fan

Machine With Heat Pump (HP)

Error 39 is displayed as soon as an electronic protection of the
fan motor is activated.

A qualified technician must examine the water heating system
and air exhaust system before the machine is put in operation
again.

DIAGNOSE:

1. Check if the contact of the
electronic protection of the
fan motor is connected when
the fan is operating (CMF –
On).

NOTE: If supply voltage
is not fed into the fan,
the protection contact is
in the open state.

If the contact is disconnected,
the fan motor is overheated
or the fan is damaged: wait
until the fan cools down - ap-
prox. 15 minutes. In case the
fault is a temperature prob-
lem and the fan is not dam-
aged, the error will not reac-
tivate when the machine is
restarted.

2. Check if the airflow is ob-
structed. Also check if the ro-
tation of the drum and fan are
obstructed/limited.

Check if the lint filter is clog-
ged, if so, clean it. Check the
heat exchangers, if clogged
with dust, clean them.

3. In case the electronic pro-
tection of the motor does not
connect within 15 minutes.

It is likely the fan is damaged,
replace the fan.

4. Check if the power supply
and control circuits of the fan
are interrupted.

If the circuits are interrupted,
repair them.

5. Check the input signal based
on the state as indicated in the
Service menu.

If the input is not functional,
replace the programmer board.

 Failure 40: Phase Error

Machine With Heat Pump (HP)

Error 40 may occur when the sequence of phases is incorrectly
connected in the power supply system.

If error 40 occurs during the operation, it is either due to a failure
of one phase of the power supply system or due to a significant
difference of voltage in the individual phases.

DIAGNOSE:

1. The fault occurred after the
machine was installed.

Change the sequence of phases
respective to the power supply
system on the machine supply
cable.

2. The fault occurred during
machine operation.

Check if unwanted failures in
the machine power supply sys-
tem occurred.

3. The fault occurred during
machine operation - check (ac-
cording to the wiring diagram)
if interruptions in the power
supply circuits of the individu-
al machine circuits occurred.

Check the state of the pilot re-
lay which monitors the phases.
If the wiring is not continuous,
repair the wiring.

Table continues...

Troubleshooting

©

 Copyright, Alliance Laundry Systems LLC -

 DO NOT COPY or TRANSMIT

  51

  Part No. D1621ENR3

Summary of Contents for SGHP190E

Page 1: ...l Identification Original Instructions Keep These Instructions for Future Reference CAUTION Read the instructions before using the machine If this machine changes ownership this manual must accompany...

Page 2: ......

Page 3: ...st a Dryer Program 22 Programming 23 General 23 Step 1 Program Menu 23 Step 2 Program Functions 23 Step 3 Program Step Functions 24 Step 4 Programming the Drying Part 25 Operation menu 28 Start Up 28...

Page 4: ...Motor Thermic 45 Failure 8 Airflow Switch Open at Start up 45 Failure 9 Airflow Switch Open After Start up 45 Failure 10 Airflow Switch Closed 46 Failure 11 Fault Cool down 46 Failure 12 No Reheating...

Page 5: ...Service information 54 General 54 Maintenance 54 Information for Service 54 Programmer Circuit Board 54 Instructions for Replacing the Electronic Board and Keypad 54 Instructions for Installing New S...

Page 6: ...ca pacity Machine type selec tion Tumble Dryer 190 Liters 9Kg T9 250 Liters 11Kg T11 285 Liters 13Kg T13 345 Liters 16Kg T16 Machine Type Selection Copyright Alliance Laundry Systems LLC DO NOT COPY...

Page 7: ...P250E IUHP250F SUHP250F UUHP250F IWHP250E SWHP250E UWHP250E IWHP250F SWHP250F UWHP250F 285 Liters 13 Kg IGHP285E SGHP285E UGHP285E IGHP285F SGHP285F UGHP285F IQHP285E SQHP285E UQHP285E IQHP285F SQHP28...

Page 8: ...ng the machine at an in correct voltage can damage the programmer The machine must not be exposed to high humidity or ex treme high and low temperatures Do not tamper with the controls INSTRUCTIONS IN...

Page 9: ...by step REVERSE Switch On Off Reverse function STOP Interrupting a program Finishing a program SERVICE shows the states and the total number of cycles of the machine CFD1307R_SVG CONFIRM THE SELECTIO...

Page 10: ...item MOISTURE LEVEL Setting for residual moisture level Table 1 Programming and Emergency Stop Switch PROGRAMMING SWITCH Programming switch is located inside the machine behind the control panel To ac...

Page 11: ...EMERGENCY STOP SWITCH The emergency stop switch is only available on non coin dryers Main Menu Warnings and Symbols Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 11 Part No D1621ENR3...

Page 12: ...program step by step Editing a dryer program step by step Adding inserting and deleting steps in the dryer program Copying a dryer program Inspecting the dryer program by the view function The CONFIGU...

Page 13: ...er Programs 5 Steps The Creation of a Dryer Program A Dryer Program is built up step by step Basic Description of Controls Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 13 Part No D16...

Page 14: ...poses a Final Cooldown sequence is added at the end of the program The Final Cooldown sequence takes 3 minutes if the tempera ture is above 50 C then the program is finished The Final Cooldown sequenc...

Page 15: ...INITIALIZATION OF THE DRYER HAS BEEN DONE AT THE FACTORY FOR THE CREATION OF NEW PROGRAMS NO CHANGES HAVE TO BE MADE IN THE INITIALIZATION OR CON FIGURATION MENUS C110 Initialization Menu HOW TO GET I...

Page 16: ...n Set the Unwrinkle On and Off Time Limits On Time 3 99 seconds Off Time 1 15 mi nutes Default value On Time 5 seconds Off Time 5 minutes Adjust the programmed time with the ARROW UP and DOWN buttons...

Page 17: ...of dryers For that reason it must be individually set up with important parameters for various machine types Ba sic machine adjusting is made in the factory WARNING Only a qualified technician should...

Page 18: ...will be cleared and the default Factory settings will be re installed This function should only be used at the initialization of a new FLEX CON TROL Dryer Computer Select Yes or No and con firm by pre...

Page 19: ...support a warning will be displayed at the end of the drying cy cle if the machine exceeds the programmed number of cycles The default value is 15 A value between 5 and 20 can be programmed Depending...

Page 20: ...ms stay in the memory of the com puter For all 20 programs default values will be loaded Select Yes or No and you have to confirm by press ing the ENTER button By selecting YES a new request for confi...

Page 21: ...erator knows which kind of dry process the pro gram corresponds with You can select the Lan guage from a list by press ing the ARROW UP or DOWN buttons and you have to confirm with the ENTER button C...

Page 22: ...How to Create and Adjust a Dryer Program Initializing the Machine Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 22 Part No D1621ENR3...

Page 23: ...ess the ARROW RIGHT button to select the Program Menu Main Menu PROGRAM Press the ENTER button to confirm your selection Goto Step 2 Program Functions Step 2 Program Functions SELECT THE PROGRAM NUMBE...

Page 24: ...you will change values or list ele ments from an existing step Press the ARROW RIGHT button if you don t want to Edit a step Select the Step number If the number is not accepted this means that the s...

Page 25: ...This paragraph gives a detailed explanation about program ming the Dryer Sequences Each program step contains a drying part and a cooldown part First the dryer part must be selected item by item can b...

Page 26: ...value is 5 The value is programmable between 0 and 30 50 70 is the residual moisture level after extrac tion in washing machine Adjust the desired Humidi ty level Press the ENTER button for confirmat...

Page 27: ...Press the ENTER button for confirmation P Pr XX Step XX TurnTime _ _ sec P Pr XX Step XX RestTime _ _ sec Only for machines executed with reversing Settings are applicable for the DRY and COOLDOWN par...

Page 28: ...see the Cooldown Sequence A row of bars shows you if the Sequence has just been start ed or if or of the Sequence time is over PrXX StYY ZZ Z Min Dry PrXX The selected program number StYY The selecte...

Page 29: ...e interrupted program are displayed The message UNLOAD will inform you if it s allowed to open the door Safety conditions If the actual temperature is too high the message TOO HOT will be displayed to...

Page 30: ...up then the air humidity will decrease bit by bit The dryer computer humidity sensor measures this value and cal culates the corresponding residual humidity of the linen The re sidual humidity is the...

Page 31: ...IMPORTANT While the dryer is running do not open and close the door it disturbs the humidity control measurement WARNING CERTAIN FABRICS CAN GET DAMAGED WHEN DRYED UNTIL A RESIDUAL HUMIDITY OF 0 BONE...

Page 32: ...Step 1 Drying A 40 R 5 Cooldown 20 Program 2 LOW 86 F 30 C 20 MIN Sequence Tempera ture Time mi nutes Reversation sec onds Step 1 Drying 86 F 30 C 20 A 40 R 5 Cooldown 3 Program 3 LOW 95 F 35 C 30 MI...

Page 33: ...9 HOT 158 F 70 C 30 MIN Sequence Tempera ture Time mi nutes Reversation sec onds Step 1 Drying 158 F 70 C 30 A 40 R 5 Cooldown 5 Program 10 HOT X F C MIN Sequence Tempera ture Time mi nutes Reversatio...

Page 34: ...40 C 25 Cool Down Step 2 Drying 102 2 F 39 C 5 Cool Down Step 3 Drying 96 8 F 36 C 6 Cool Down Table 3 Program 14 All In One Sequence Temperature Humidity Time minutes Reversation seconds Step 1 Dryi...

Page 35: ...n Step 2 Drying 96 8 F 36 C 10 Cool Down Step 3 Drying 105 8 F 41 C 15 Cool Down Table 5 Program 16 No Heating Sequence Temperature Humidity Time minutes Reversation seconds Step 1 Drying 95 F 35 C 10...

Page 36: ...ill fulfil a cooldown sequence Actual tempera ture 50 C If at the end of the cycle the safety conditions are not fulfilled Temperature 50 C the message TOO HOT will be dis played TOO HOT MESSAGE IS ER...

Page 37: ...s possi ble to adjust the number of cycles for which the warning is generated in the Configuration menu Only by opening the lint door the Lint Filter Door Cycle Counter will be reset By opening the D...

Page 38: ...Temperature sen sor 2 Value out of range Continue Don t start Before Start up E21 Heating element overheat ing Safety Heating element trips Heating Off Full Stop at safe temperature Whole cycle E25 N...

Page 39: ...GHT button to select the SERVICE menu Main Menu Service Press the ENTER button to make your selection Now you will see the first menu item By pressing the ARROW LEFT or RIGHT button you can see the me...

Page 40: ...responds with Input 2 Input 20 the State that corresponds with Input 20 Analog Input 1 2 3 the value that corresponds with Analog Input 1 2 3 The exact function of the inputs can be found on the elec...

Page 41: ...ram Mode The Main menu is now available Press the ARROW RIGHT button to select the Diagnostic menu Main Menu Diagnostic Press the ENTER button to make your selection D Diagnostic Pro gram No If you do...

Page 42: ...ode The machine is not responding on pressing the keyboard buttons The programming switch is not functional Check if the input connector A is well connected and check the wiring between the input conn...

Page 43: ...stem If the output relay is not func tional replace the control board 8 Check the input Signal by monitoring the state at the Service menu If the input is not functional anymore replace the control bo...

Page 44: ...he contact will be closed again automatically af ter some time Failure 5 occurs for 1 motor machines NC ther mal contact A skilled and experienced technician must examine the motor drive system before...

Page 45: ...en the ventilator is not functional or if the airflow is obstructed Failure 8 occurs only at start up NO contact The Airflow Switch has a safety function and it must not be ob structed A skilled and e...

Page 46: ...m before the machine is put in operation again DIAGNOSE 1 Check if the airflow detec tion system is still functional If the airflow detection system or the switch is out of order it must be repaired o...

Page 47: ...output relay that controls the heating system If the output relay is not func tional replace the control board Failure 14 Heat time Failure 14 occurs when after X minutes the target temperature is no...

Page 48: ...on the power fault mes sage 19 will be generated again A skilled and experienced technician must examine the heating and air outlet system before the machine is put in operation again DIAGNOSE 1 Check...

Page 49: ...If the input of the controller board is not functional re place the controller board first check previous items Failure 26 No Humidity Sensor Cap HUMIDITY CONTROL ONLY Failure 26 occurs when the dust...

Page 50: ...perienced technician must examine the heating and air outlet system before the machine is put in operation again DIAGNOSE 1 Check the air outlet system If the air flow is not sufficient adjust the air...

Page 51: ...the fan motor is overheated or the fan is damaged wait until the fan cools down ap prox 15 minutes In case the fault is a temperature prob lem and the fan is not dam aged the error will not reac tiva...

Page 52: ...MADE TO RUN WITHOUT LOAD OR WITH A VERY SMALL LOAD THE SYSTEM CAN ONLY FUNCTION IN A NORMAL WAY WHEN THERE IS SUFFICIANT EVAP ORATION TO BE MEASURED BY THE AIR HUMIDITY SENSOR C133 WARNING CHECK CORRE...

Page 53: ...at the same kind of linen is sorted and dryed together Coton Synthetic In case of Humidity Con trol a mixture of all kinds of linen will not give a good overall drying result Thin Thick Fabrics Thick...

Page 54: ...e software This data along with the machine serial no order code must be given in all correspondence or inquiries to the manufacturer C085 XXX VVV XXX Software for the FLEX CONTROL dryer computer VVV...

Page 55: ...er Switch on the main power The display should illuminate If the software is compatible with the previous software the new software can be used without reinitialization You have to clear all the error...

Page 56: ...Version Software Date Keyboard MACHINE CONFIGURATION DATA FUNCTION DATA ENTERED Machine Type Brightness Display Heating Type O Heat Pump Reversing System O Yes O No Humidity Control Sys tem O Yes O N...

Page 57: ...O 19 O 20 Set Unwrinkle Time Minutes Unwrinkle On Time Seconds Unwrinkle Off Time Minutes Service Interval Buzzer Time Seconds Allow Advance O Yes O No Manual Override O Yes O No Default Motor Turn Ti...

Reviews: