Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
9
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Step 2: Mount the Drive
Accessing the Terminals
Opening the Cover
Cable Entry Plate Removal
If additional wiring access is needed, the Cable Entry Plate on 0…3 Frame drives
can be removed. Simply loosen the screws securing the plate to the chassis. The
slotted mounting holes assure easy removal.
Power Wiring Access Panel Removal
Environment
Operating Temperatures
PowerFlex 700 drives are designed to operate at 0 to 40 °C ambient. To operate
the drive in installations between 41 and 50 °C (106…122 °F), see
Table 2
and
refer to pages
34
through
41
for exceptions.
IMPORTANT
Removing the Cable Entry Plate limits the maximum ambient temperature to
40 °C (104 °F).
Frame
Removal Procedure
(Replace when wiring is complete)
0, 1, 2 & 6
Part of front cover, see above.
3
Open front cover and gently tap/slide cover down and out.
4
Loosen the 4 screws and remove.
5
Remove front cover (see above), gently tap/slide panel up and out.
Esc
7
8
9
4
5
6
1
2
3
.
0
+/-
Sel
Jog
Alt
POWER
STS
PORT
MOD
NET A
NET B
Exp
Param #
S.M.A.R.T.
Exit
Lang
Auto / Man
Remove
HOT surfaces can cause severe burns
CAUTION
Frames 0…4
Locate the slot in the upper left corner. Slide the locking
tab up and swing the cover open. Special hinges allow
cover to move away from drive and lay on top of adjacent
drive (if present). See below for frame 4 access panel
removal.
Frame 5
Slide the locking tab up, loosen the right-hand cover
screw and remove. See below for access panel removal.
Frame 6
Loosen 2 screws at bottom of drive cover. Carefully slide
bottom cover down & out. Loosen the 2 screws at top of
cover and remove.