![Allen-Bradley powerflex 700 Installation Instructions Manual Download Page 28](http://html1.mh-extra.com/html/allen-bradley/powerflex-700/powerflex-700_installation-instructions-manual_2900263028.webp)
28
Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Power Terminal Blocks
No.
Name
Frame
Description
Wire Size Range
(2)
(2)
Maximum/minimum wire sizes that the terminal block accepts
- these are not recommendations.
Torque
Maximum
Minimum
Maximum
Recommended
➊
Power
Terminal
Block
0…1
Input power and
motor connections
4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
1.7 N•m
(15 lb•in)
0.8 N•m
(7 lb•in)
2
Input power and
motor connections
10.0 mm
2
(8 AWG)
0.8 mm
2
(18 AWG)
1.7 N•m
(15 lb•in)
1.4 N•m
(12 lb•in)
3
Input power and
motor connections
25.0 mm
2
(3 AWG)
2.5 mm
2
(14 AWG)
3.6 N•m
(32 lb•in)
1.8 N•m
(16 lb•in)
BR1, 2 terminals
10.0 mm
2
(8 AWG)
0.8 mm
2
(18 AWG)
1.7 N•m
(15 lb•in)
1.4 N•m
(12 lb•in)
4
Input power and
motor connections
35.0 mm
2
(2 AWG)
10.0 mm
2
(8 AWG)
4.0 N•m
(35 lb•in)
4.0 N•m
(35 lb•in)
5
75Hp,480V
100Hp,600V
Input power, DC+,
DC–, BR1, 2, PE,
motor connections
50.0 mm
2
(1/0 AWG)
4.0 mm
2
(12 AWG)
See Note
(4)
(4) Refer to the terminal block label inside the drive.
5
100Hp
Input power, DC+,
DC– and motor
70.0 mm
2
(2/0 AWG)
10.0 mm
2
(8 AWG)
BR1, 2, PE terminals 50.0 mm
2
(1/0 AWG)
4.0 mm
2
(12 AWG)
6
Input power, DC+,
DC–, BR1, 2, PE,
motor connections
150.0 mm
2
(300 MCM)
see Note
(3)
(3) If can be necessary to connect multiple wires in parallel to these terminals by using multiple lugs.
2.5 mm
2
(14 AWG)
6.0 N•m
(52 lb•in)
6.0 N•m
(52 lb•in)
➋
SHLD
Terminal
0…6
Terminating point
for wiring shields
—
—
1.6 N•m
(14 lb•in)
1.6 N•m
(14 lb•in)
➌
AUX
Terminal
Block
0…4
Auxiliary Control
Voltage
PS+, PS–
(1)
(1) External control power: UL Installation-300V DC, ±10%, Non UL Installation-270…600V DC, ±10%
0…3 Frame - 40 W, 165 mA, 5 Frame - 80 W, 90 mA. Refer to the User Manual for further information.
1.5 mm
2
(16 AWG)
0.2 mm
2
(24 AWG)
—
—
5…6
4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
➍
Fan
Terminal
Block
5…6
User Supplied Fan
Voltage
4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m