Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
53
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
I/O Terminals
The figure below shows the I/O Control Cassette and terminal block locations.
The cassette provides a mounting point for the various PowerFlex 700
I/O options. To remove the cassette, follow the steps below. Cassette removal is
similar for all frames (Frame 0 drive shown).
PowerFlex 700 Typical Cassette & I/O Terminal Blocks
I/O Terminal Block Specifications
Step
Description
Disconnect the two cable connectors shown below.
Loosen the two screw latches shown below.
Slide the cassette out.
Remove screws securing cassette cover to gain access to the boards.
No.
Name
Description
Wire Size Range
(1)
(1) Maximum/minimum that the terminal block accepts - these are not recommendations.
Torque
Maximum
Minimum
Maximum
Recommended
➊
I/O Cassette
Removable I/O Cassette
➋
I/O Terminal Block
Signal & control
connections
2.5 mm
2
(14 AWG)
0.30 mm
2
(22 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
➌
Encoder Terminal
Block
Encoder power & signal
connections
0.75 mm
2
(18 AWG)
0.196 mm
2
(24 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
A
B
C
D
BR1
BR2
DC+
DC-
PE
U/T1
V/T2
W/T3
R/L1
L2
➌
➋
➊
=
A
Pin 1
Detail
B
C
D
B