Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
47
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Fram
e
Vo
lt
ag
e
Code
Current
Ra
ti
ng
Factory Default Jumper Settings
Power Source Type
MOV/Input
Filter Caps
(1) (2)
DC Bus Common
Mode Caps
5
IP20, NEMA/UL Type 1 and Open Drives (continued)
C
F
W
140
052
060
Two green/yellow
wires connected to
the Power
Terminal Block rail
Green/yellow wire to
CM Cap Board is
connected to ground
Solid Ground
1. CM Cap jumper wire must be connected to
ground with a metal screw. Verify, and if
necessary, remove the nylon screw/spacer and
insert a metal M5 x 8 screw. Torque to 3.2 N•m
(28 lb•in).
2. MOV/Input Filter Cap jumper wires must be
connected to ground with a metal screw.
Verify, and if necessary, remove the nylon
screw/spacer and insert a metal M5 x 12
screw.
Non-Solid Ground
1. CM Cap jumper wire must be insulated from
ground with a nylon screw/spacer. Verify, and
if necessary, remove the metal screw and
insert a M5 x 15 nylon screw/spacer.
2. MOV/Input Filter Cap jumper wires must be
insulated from ground with a nylon screw/
spacer. Verify, and if necessary, remove the
metal screw and insert a
M5 x 20 nylon screw/spacer.
E
F
T
W
077
082
099
098
Two green/yellow
wires connected to
chassis ground
Green/yellow wire to
CM Cap Board is
connected to ground
Solid Ground
1. CM Cap jumper wire must be connected to
ground with a metal screw. Verify, and if
necessary, remove the nylon screw/spacer and
insert a metal M5 x 8 screw. Torque to 3.2 N•m
(28 lb•in).
2. MOV jumper wire must be connected to
ground with metal screws. Verify, and if
necessary, remove the nylon screw/spacers
and insert a metal M5 x 12 screws.
3. Input Filter Cap jumper wire must be
connected to ground with a metal screw.
Verify, and if necessary, remove the nylon
screw/spacer and insert metal M5 x 8 screw.
Non-Solid Ground
1. CM Cap jumper wire must be insulated from
ground with a nylon screw/spacer. Verify, and
if necessary, remove the metal screw and
insert a M5 x 15 nylon screw/spacer.
2. MOV jumper wire must be insulated from
ground with a nylon screw/spacer. Verify, and
if necessary, remove the metal screws and
insert a M5 x 20 nylon screw/spacer.
3. Input Filter Cap jumper wire must be insulated
from ground with a nylon screw/spacer. Verify,
and if necessary, remove the metal screws and
insert a M5 x 15 nylon screw/spacer.
Frame 5 continued on next page
(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT AC
OUTPUT
Optional
Communications
Module
9
CM Cap
MOV
MOV / Input Filter Cap
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT AC
OUTPUT
Optional
Communications
Module
9
PE
CM Cap
MOV
MOV
Input Filter
Cap