Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
49
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Fram
e
Vo
lt
ag
e
Code
Current
Ra
ti
ng
Factory Default Jumper Settings
Power Source Type
MOV/Input
Filter Caps
(1) (2)
DC Bus Common
Mode Caps
5
IP54, NEMA Type 12 Drives (continued)
E
F
T
W
All
Two green/yellow
wires connected
to chassis ground
Green/yellow wire to
CM Cap Board is
connected to ground
Solid Ground
1. CM Cap jumper wire must be connected to
ground with a metal screw. Verify, and if
necessary, remove the nylon screw/spacer and
insert a metal M5 x 12 screw. Torque to 3.2
N•m (28 lb•in).
2. MOV/Input Filter Cap jumper wires must be
connected to ground with a metal screw.
Verify, and if necessary, remove the nylon
screw/spacer and insert a metal M5 x 12
screw.
Non-Solid Ground
1. CM Cap jumper wire must be insulated from
ground with a nylon screw/spacer. Verify, and
if necessary, remove the metal screw and
insert a M5 x 20 nylon screw/spacer.
2. MOV/Input Filter Cap jumper wires must be
insulated from ground with a nylon screw/
spacer. Verify, and if necessary, remove the
metal screw and insert a M5 x 20 nylon screw/
spacer.
(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.
USE 75 C CU WIRE ONLY
WIRE RANGE: 4-3/0 AWG (18-70 MM2)
TORQUE: 133 IN-LB (15 N-M)
STRIP LENGTH: 1.02 IN (26 MM)
POWER & DC TERMINAL RATINGS
WIRE RANGE: 14-1/0 AWG (2.5-50 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
BRAKE TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (18-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
OUTPUT
INPUT AC
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
DANGER
DANGER
RISK OF ELECTRIC
SHOCK AND DEATH
FIELD INSTALLED OPTIONS
6 MM HEX KEY
6 MM HEX KEY
SHLD
SHLD
CM Cap
MOV
MOV / Input Filter Cap