Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
129
Go Online with the Controller
Chapter 7
Download
Follow these steps to transfer your project from your computer to your
controller.
1. Turn the key switch of the controller to REM.
2. Open the controller project that you want to download.
3. Define the path to the controller.
a. Click Who Active
.
b. Select the controller.
To open a level, click the + sign. If a controller is already selected,
make sure that it is the correct controller.
4. Click Download.
The Logix Designer application compares the following information in
the offline project and the controller:
• Controller serial number (if project to controller match is selected)
• Firmware major and minor revisions
• Safety status
• Safety task signature (if one exists)
• Safety-lock status
Controller
Project
Download