Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 3
Configure the Controller
Table 16 - Additional Resources
Electronic Keying
Electronic Keying reduces the possibility that you use the wrong device in a
control system. It compares the device defined in your project to the installed
device. If keying fails, a fault occurs. These attributes are compared.
The following Electronic Keying options are available.
TIP
You can use the Controller Properties dialog box to change the controller
from standard to safety, or safety to standard, by clicking the Change
Controller button. However, standard and safety projects are substantially
affected.
See
, for details on the ramifications of
changing controllers.
Resource
Description
,
Contains more information on the safety task, safety
programs, and safety routines.
,
Provides more information on managing the SSN.
Attribute
Description
Vendor
The device manufacturer.
Device Type
The general type of the product, for example, digital I/O module.
Product Code
The specific type of the product. The Product Code maps to a catalog number.
Major Revision
A number that represents the functional capabilities of a device.
Minor Revision
A number that represents behavior changes in the device.
Keying Option
Description
Compatible
Module
Lets the installed device accept the key of the device that is defined in the project when the
installed device can emulate the defined device. With Compatible Module, you can typically
replace a device with another device that has the following characteristics:
• Same catalog number
• Same or higher Major Revision
• Minor Revision as follows:
– If the Major Revision is the same, the Minor Revision must be the same or higher.
– If the Major Revision is higher, the Minor Revision can be any number.
Exact Match
Indicates that all keying attributes must match to establish communication. If any attribute
does not match precisely, communication with the device does not occur. Exact Match is
required if you are using Firmware Manager.
Summary of Contents for GuardLogix 5570
Page 8: ...8 Rockwell Automation Publication 1756 UM022D EN P May 2017 Table of Contents...
Page 20: ...20 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 1 System Overview Notes...
Page 169: ...Rockwell Automation Publication 1756 UM022D EN P May 2017 169 Index Notes...
Page 170: ...170 Rockwell Automation Publication 1756 UM022D EN P May 2017 Index Notes...
Page 171: ......