Communicate over Networks
The Safety Network
The CIP Safety protocol is an end-node to end-node safety protocol that
provides routing of CIP Safety messages to and from safety I/O devices
through bridges, switches, and routers.
To maintain high integrity when routing through standard bridges, switches, or
routers, each end node within a routable CIP Safety Control System must have
a unique reference. This unique reference is a combination of a safety network
number (SNN) and the node address of the network device.
Manage the Safety Network Number (SNN)
The SNN assigned to safety devices on a network segment must be unique.
You must be sure that a unique SNN is assigned to the following:
• Each CIP Safety network that contains safety devices
• Each chassis that contains one or more GuardLogix® controllers
Topic
Page
TIP
Multiple safety network numbers can be assigned to a CIP Safety subnet
or a ControlBus chassis that contains more than one safety device.
However, for simplicity, we recommend that each CIP Safety subnet has
only one unique SNN.