16
Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 1
System Overview
Select System Hardware
The GuardLogix system supports SIL 3 and PLe safety applications. The
GuardLogix controller is composed of a primary controller and a safety partner
that function together in a 1oo2 architecture.
lists catalog numbers for
primary controllers and safety partners.
The safety partner must be installed in the slot immediately to the right of the
primary controller. The firmware major and minor revisions of the primary
controller and safety partner must match exactly to establish the control
partnership that is required for safety applications.
Primary Controller
The primary controller is the processor that performs standard and safety
functions and communicates with the safety partner for safety-related
functions in the GuardLogix control system. Standard functions include the
following:
• I/O control
• Logic
• Timing
• Counting
• Report generation
• Communication
• Arithmetic computations
• Data file manipulation
The primary controller consists of a central processor, I/O interface, and
memory.
Table 4 - Primary Controller and Corresponding Safety Partner Catalog Numbers
Primary Controller
Safety Partner
1756-L71S, 1756-L72S, 1756-L73S
1756-L7SP
1756-L73SXT
1756-L7SPXT
Table 5 - Memory Capacity
Cat. No.
User Memory (RAM capacity)
Standard Tasks and Components
Safety Task and Components
1756-L71S
2 MB
1 MB
1756-L72S
4 MB
2 MB
1756-L73S,1756-L73SXT
8 MB
4 MB
Summary of Contents for GuardLogix 5570
Page 8: ...8 Rockwell Automation Publication 1756 UM022D EN P May 2017 Table of Contents...
Page 20: ...20 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 1 System Overview Notes...
Page 169: ...Rockwell Automation Publication 1756 UM022D EN P May 2017 169 Index Notes...
Page 170: ...170 Rockwell Automation Publication 1756 UM022D EN P May 2017 Index Notes...
Page 171: ......