Publication 1794-6.5.11 - November 1997
Specifications
A
-3
Dimensions
Inches
(Millimeters)
1.8H x 3.7W x 2.1D
(45.7 x 94.0 x 53.3)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
0 to 55°C (32 to 131
o
F)
–40 to 85°C (–40 to 185°F)
5 to 95% noncondensing (operating)
5 to 80% noncondensing (nonoperating)
30 g peak acceleration, 11(
±
1)ms pulse width
50 g peak acceleration, 11(
±
1)ms pulse width
Tested 5 g @ 10-500Hz per IEC 68-2-6
Input Conductors
Wire
Category
Length (max)
Belden 8761
2
1
1000ft (304.8m)
Output Conductors
Wire
Category
Belden 8761
2
1
Agency Certification
(when product is marked)
• CSA certified
• CSA Class I, Division 2
Groups A, B, C, D certified
• UL listed
• CE marked for all applicable directives
User Manual
Publication 1794-6.5.11
1
Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1,
“Industrial Automation Wiring and Grounding Guidelines for Noise Immunity.”
Specifications – 1794-IJ2 Frequency Input Module