Publication 1794-6.5.11 - November 1997
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
5
-7
Write
Word 1
Bits 00-01
Missing pulse multiplier bits (channel 1) – used to modify the Minimum Frequency Sampling Time to allow the frequency
bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more
quickly.
Default
= no multiplier; alarm generated immediately
Bit
01
00
Missing Pulse Multiplier
0
0
No Multiplier, alarm generated immediately (normal mode with 2s delay)
0
1
X2
1
0
X8
1
1
X32
Bits 02-04
Number of pulses to terminate sampling (channel 1) – Lets you calculate Frequency when a specified number of input pulses
have occurred. This allows earlier reporting of the frequency than the Minimum Frequency Sampling Time, when many input
pulses are occurring. Accurate frequency determination is possible without waiting for the full Minimum Frequency Sampling
Time to expire.
Default
= minimum frequency sampling time.
Bit
04
03
02
Number of pulses to terminate sampling
0
0
0
Use minimum frequency sampling time
0
0
1
2
0
1
0
4
0
1
1
8
1
0
0
16
1
0
1
32
1
1
0
64
1
1
1
128
Bits 05
Frequency range bits (channel 1) – Specifies the Frequency Range of the Frequency input.
0 = 1-32767 (below 1Hz reports 0);
1 = 1.0-3276.7 (below 1.0Hz reports 0.0).
Default
= 0
Bit 06
Local fault mode selection – determines how the Module Safe State data will be used to control alarm outputs for bus
communication and internal module faults (local fault = Wire Off Fault or Missing Pulse Alarm).
0 = safe states activated by bus communication only;
1 = safe states activated by any failure (bus communication, internal module faults, etc.)
Default
= 0, safe states activated by bus communication only
Bit 07
Not used
Bits 08-09
(10-11)
Missing pulse multiplier bits (channel 0)– used to modify the Minimum Frequency Sampling Time to allow the frequency
bandwidth to be more closely adjusted to the value needed to report the proper frequency and report a missing pulse more
quickly.
Default
= no multiplier; alarm generated immediately
Bit
09
(11)
08
(10)
Minimum frequency sampling time
0
0
No Multiplier, alarm generated immediately (normal mode with 2s delay)
0
1
X2
1
0
X8
1
1
X32
Word
Bit
Definition