Publication 1794-6.5.11 - November 1997
Programming Your Frequency Input Module
3
-5
Chapter Summary
In this chapter, you learned how to program your IJ2 input module using
block transfer instructions and ladder logic. Now, you can configure your
module.
EN
BTR
BLOCK TRANSFER READ
Rack
Group
Slot
Control Block
14
1
0
BR141:0
DN
Data File
BT Length
Continuous
2BTD5:101
0
NO
ER
EN
BTW
BLOCK TRANSFER WRITE
Rack
Group
Slot
Control Block
14
1
0
BW141:0
DN
Data File
BT Length
Continuous
2BTD5:1
0
NO
ER
BR141:0
EN
BR141:0
EN
BW141:0
EN
Rung 1STEPO:1
The IJ2 module is located in rack 14, I/O group 1, slot 0. The data obtained by the PLC-5/250 processor from the
IJ2 module is placed in the data table starting at 2BTD5:101, and with the default length of 0, is 7 words long. The
length can be any number between 0 and 7.
BW141:0
EN
Rung 1STEPO:1
The IJ2 module is located in rack 14, I/O group 1, slot 0. The data sent to the IJ2 module from the PLC-5/250 processor
is from the data table starting at 2BTD5:1, and with a default length of 0, is 8 words long.
Valid BTW lengths can be any number between 0 and 8.
IJ2 BTR
Enable Bit
IJ2 BTW
Enable Bit
IJ2 BTR
Control File
IJ2 BTR
Enable Bit
IJ2 BTW
Enable Bit
IJ2 BTW
Control File
BT Timeout
4
BT Timeout
4
PLC-5/250 Processor
Program Example
Configure the
IJ2 Module
4