Publication 1794-6.5.11 - November 1997
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
4
-5
Block Transfer Write Word Assignments for the Frequency
Input Module
Word 5
Bits 00-03
Diagnostic Status – indicate the response from the module; a normal or non-normal operating condition.
Bit
03
02
01
00
0
0
0
0
0 = Normal Operation (No Failure)
0
0
0
1
1 = Calibration Failure
0
0
1
0
2 = Configuration Failure
A Minimum Frequency Sample Time value other than 0-9 was selected.
0
0
1
1
3 = Message Failure
0
1
0
0
4 = Lead Break Detection Hardware Failure
0
1
0
1
5 = Major Hardware Failure
0
1
1
0
6 = EEPROM Failure
0
1
1
1
7 = RAM Failure
1
0
0
0
8 = ROM Failure
1
0
0
1
9 = Calculation Failure
The actual Frequency is greater than 32,767 Hz. or 3,276.7 Hz. (overange).
The scaled Frequency is greater than 32,767 Hz. or 3,276.7 Hz. (overange).
The % Full Scale calculation (based on Maximum Frequency) is
>
3,276.7%.
1010-1111
10 – 15 = Not Used
Bits 04-15
(04-17)
Reserved
Word
Bit
Definition
(Octal Bit)
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
0
CF
SSM
FR
Ch 0
Number Of Pulses To
Terminate Sampling
Ch 0
MPM
Ch 0
R
LF
FR
Ch 1
Number Of Pulses To
Terminate Sampling
Ch 1
MPM
Ch 1
1
Maximum Frequency 0 – 32,767 – or – 0.0 – 3,276.7 – or – Absolute Value of Acceleration 0 to 32,767 – Channel 0
2
Frequency Scaling Divisor 0 – 255 Ch 0
Frequency Scaling Multiplier 0 – 255 Ch 0
3
WOFG
Ch 0
WOFF
Ch 0
IGI
Ch 0
IFI
Ch 0
Minimum Frequency
Sample Time
Ch 0
Init St
Up
Ch 0
ACT Ch 0
F/A AS
Ch 0
MPDM
Ch 0
WOFM
Ch 0
4
Maximum Frequency 0 – 32,767 – or – 0.0 – 3,276.7 – or – Absolute Value of Acceleration 0 to 32,767 – Channel 1
5
Frequency Scaling Divisor 0 – 255 Ch 1
Frequency Scaling Multiplier 0 – 255 Ch 1