
Publication 1794-6.5.11 - November 1997
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
5
-11
Word 7
Bits 00-01
Wire-Off/Missing Pulse fault select mode (channel 1) –
Sets the mode for 24 Vdc IEC 1+ Wire Off Input Detection and Missing
Pulse Detection result for any input (Frequency or Gate). The Maximum Frequency is determined by Frequency Range bit and
the Maximum Frequency value, and the Minimum Frequency is determined by Frequency Range bit. The Wire Off detect time
(in mode 1, 2, & 3) is 2 seconds maximum.
Bits 00-01
Bit
01
00
Channel wire-off/missing pulse fault mode
0
0
Disabled
0
1
Alarm only (frequency unchanged)
1
0
Alarm and force frequency to maximum frequency value (32767 or 3276.7 or maximum frequency
value
≠
0).
1
1
Alarm and force frequency to minimum frequency value (0 or 0.0).
Bits 02-03
Missing pulse delay multiplier bits (channel 1)– Specifies the number of Missing Pulse Alarms periods (Minimum Frequency
Sampling Times) which will be tolerated before the alarm is actually generated, if enabled. (Used to defeat the Missing Pulse
Alarm during a system startup.)
Default
= 0 – No multiplier; alarm generated immediately (normal mode with 2s extension delay)
Bit
03
02
Alarm periods before alarm generated
0
0
No multiplier; alarm generated immediately (normal mode with 2s extension delay)
0
1
2 sample p 2s delay before alarm
1
0
8 sample p 2s delay before alarm
1
1
32 sample p 2s delay before alarm
Bit 04
Frequency or Acceleration Alarm Select (channel 1)– Determines if the value in the Maximum Frequency or Acceleration write
word is a Frequency (actual or scaled) or Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = frequency alarm
1 = acceleration alarm
Default
= 0 – frequency alarm
Bits 05-06
Acceleration Calculation Time (channel 1) – Specifies the number of Frequency Sample Times over which the module
calculates acceleration.
Default
= 0 – Rolling Average (previous 4 samples)
Bit
06
05
Acceleration Calculation Time in Frequency Sample Times
0
0
Rolling Average (previous 4 samples)
0
1
8
1
0
16
1
1
32
Bit 07
Initiate Startup Select (channel 1) – Alerts a channel that if process start up is in progress to defeat the missing pulse alarm
for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default
= 0 – Normal Run Mode
Word
Bit
Definition