Publication 1794-6.5.11 - November 1997
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
4
-9
Word 3
Bits 05-06
Acceleration Calculation Time (channel 0) – Specifies the number of Frequency Sample Times over which the module
calculates acceleration.
Default
= 0 – Rolling Average (previous 4 samples)
Bit
06
05
Acceleration Calculation Time in Frequency Sample Times
0
0
Rolling Average (previous 4 samples)
0
1
8
1
0
16
1
1
32
Bit 07
Initiate Startup Select (channel 0) – Alerts a channel that if process start up is in progress to defeat the missing pulse
alarm for a time determined by the missing pulse delay multiplier.
0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default = 0 – Normal Run Mode
Bits 08-11
(10-13)
Minimum Frequency Sampling Time (channel 0) – Specifies the minimum time (in ms) the module will spend collecting
pulses to determine the Frequency.
Bit
11
(13)
10
(12)
09
(11)
08
(10)
Minimum Frequency Sampling Time – in ms
0
0
0
0
2
0
0
0
1
4
0
0
1
0
5
0
0
1
1
10
0
1
0
0
20
0
1
0
1
50
0
1
1
0
100
0
1
1
1
200
1
0
0
0
500
1
0
0
1
1000
1010 to 1111 not used – 2ms default sample time used
Word
Bit
Definition