Publication 1756-UM050A-EN-P - December 2001
7-18
Using Produced and Consumed Tags
Download the Configuration to the Consumer
You must now load the configuration parameters to the Consumer
controller. Note that no ladder logic is required for routing in the
Consumer. The logic can consist of a single “End” rung.
1.
Click on the
Communications
menu and select
Who Active
.
The
Who Active
window will open (Your window will display the
drivers and devices you have installed).
2.
Select your Ethernet driver (e.g., AB_ETH-1) and expand the tree
through the backplane of the consumer’s ControlLogix chassis.
3.
Highlight the Logix 5550 controller and click on the
Download
button. You will see a message similar to the following:
4.
Click on the
Download
button.