Publication 1756-UM050A-EN-P - December 2001
5-8
Using Rack Optimized I/O
6.
Click on the
Finish
button to accept the configuration. The remote
1756-ENBT module will appear indented under the local
1756-ENBT in the I/O Configuration folder.
Add the Remote I/O Modules to the I/O Configuration
You must now add the remote I/O modules to the I/O Configuration
List under the remote 1756-ENBT module.
In this example, you will add a a 1756-IB16I digital input module and
a 1756-OB16I digital output module with standard configurations. Use
these steps as a guide when you are configuring different I/O
modules for your actual system.
Add the Remote Digital Input Module
1.
Right click on the remote
1756-ENBT
module under the I/O
Configuration folder and select
New Module
.
TIP
This example application uses the I/O module
default configurations. For information on altering
the default configurations see the
ControlLogix
Digital I/O Module User Manual
, publication
1756-6.5.8.
Summary of Contents for ControlLogix 1756-ENBT
Page 1: ...ControlLogix Ethernet Bridge Module 1756 ENBT User Manual AB Parts...
Page 4: ......
Page 10: ...Publication 1756 UM050A EN P December 2001 P 6 About This User Manual Notes...
Page 20: ...Publication 1756 UM050A EN P December 2001 1 6 About the 1756 ENBT Module...
Page 64: ...Publication 1756 UM050A EN P December 2001 5 18 Using Rack Optimized I O...
Page 96: ...Publication 1756 UM050A EN P December 2001 7 20 Using Produced and Consumed Tags...
Page 130: ...Publication 1756 UM050A EN P December 2001 E 2 Autonegotiation Requirements...
Page 136: ...Publication 1756 UM050A EN P December 2001 Glossary 6 Notes...
Page 140: ...Publication 1756 UM050A EN P December 2001 4 Index...
Page 143: ...AB Parts...