Publication 1756-UM050A-EN-P - December 2001
6-12
Using Analog I/O with Direct Connection
Test the Example
Application
Use the following procedure to test the operation of the remote
analog output:
1.
Connect a voltmeter across the channel 0 output of the 1756-OF8
analog output module as shown in the following figure:
2.
Restore
RSLogix5000
and place the controller in
Run
mode.
3.
Measure the output voltage of channel 0. You should see it slowly
rise to approximately 10V, reset to zero, start rising again, etc.
This completes the Direct Connect I/O example.
What’s Next?
The following chapter describes an example application in which one
controller sends a message to another controller using produced and
consumed tags.
TIP
Refer to the
ControlLogix Analog I/O Module User
Manual
, publication 1756-6.5.9, for assistance in
wiring and debugging the I/O modules.
VOUT-0
RTN
1
5
1756-OF8
V
+
–
Summary of Contents for ControlLogix 1756-ENBT
Page 1: ...ControlLogix Ethernet Bridge Module 1756 ENBT User Manual AB Parts...
Page 4: ......
Page 10: ...Publication 1756 UM050A EN P December 2001 P 6 About This User Manual Notes...
Page 20: ...Publication 1756 UM050A EN P December 2001 1 6 About the 1756 ENBT Module...
Page 64: ...Publication 1756 UM050A EN P December 2001 5 18 Using Rack Optimized I O...
Page 96: ...Publication 1756 UM050A EN P December 2001 7 20 Using Produced and Consumed Tags...
Page 130: ...Publication 1756 UM050A EN P December 2001 E 2 Autonegotiation Requirements...
Page 136: ...Publication 1756 UM050A EN P December 2001 Glossary 6 Notes...
Page 140: ...Publication 1756 UM050A EN P December 2001 4 Index...
Page 143: ...AB Parts...